Abstract

Koordinasi proteksi adalah pemilihan atau pengaturan dari peralatan pengaman yang bertujuan untuk mengisolasi hanya bagian dari sistem yang terjadi gangguan. Gangguan pada sistem tenaga listrik sangat bervariasi besar dan jenisnya. Koordinasi sistem proteksi yang baik akan mengisolasi daerah gangguan dan mencegah pemadaman di daerah lain. Hal ini dapat meningkatkan keandalan sistem dengan menjaga kontinuitas suplai pada beban. Untuk menjaga dan meningkatkan performa sistem proteksi perlu dilakukan suatu studi terhadap koordinasi rele pengaman yang terpasang. Tugas Akhir ini bertujuan untuk menyajikan analisis terhadap koordinasi rele pengaman pada pabrik PT. Linde Indonesia Gresik. Dari 5 tipikal koordinasi yang dianalisis dapat diketahui bahwa ada beberapa kesalahan koordinasi pada setelan (setting) pick-up dan time delay. Dari hasil analisis dalam tugas akhir ini, direkomendasikan penyetelan ulang rele dan pada proteksi ground fault hanya menggunakan kurva definit. Selain itu rekomendasi lainnya penambahan rele reverse power pada bus 3 untuk mengantisipasi jika terjadi gangguan pada grid PLN yang berintegrasi dengan sistem kelistrikan PT. Linde Indonesia Gresik.
=============================================================================================================================
Coordination of protection is the selection or arrangement of the safety equipment that aims to isolate just a part of that system disruption. Disorders of the power system is very large and varied kind. Coordinating a good protection system will isolate the area and prevents fault suppression in other areas. This can improve system reliability by maintaining continuity of supply to the load. To maintain and improve the performance of protection systems need to be done a study on the coordination of safety relays installed. This final project aims to present an analysis of the safety relay coordination in the PT. Linde Indonesia Gresik. From 5 typical coordination is analyzed it can be seen that there is some error coordination in setting (setting) pick-up and time delay. From the analysis in this thesis, it is recommended to reset the relay and ground fault protection using only definite curve. Besides other recommendation is additioning of reverse power relay at bus 3 to anticipate the PLN grid disturbances in the electrical system that integrates with PT. Linde Indonesia Gresik.

Item Type: Thesis (Other)
Additional Information: RSE 621.317 Sat a-1, 2014
Uncontrolled Keywords: oordinasi, rele pengaman, gangguan, coordination, protection relay, fault
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays. Protective relays--Security measures.
Divisions: Faculty of Industrial Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis