Ulhaq, Rakhananta (2024) Optimasi Building Automation System Untuk Kontrol Chiller Menggunakan Metode Sequencing Control Di Rumah Sakit X. Diploma thesis, Institut Teknologi Sepuluh Nopember.
Text
2040201100_Undergraduate_Thesis.pdf - Accepted Version Restricted to Repository staff only until 1 October 2026. Download (4MB) | Request a copy |
Abstract
Rumah Sakit X, sebuah pusat pelayanan kesehatan utama di Surabaya, mengalami tantangan yang signifikan dalam operasionalnya yang berkaitan dengan pengelolaan chiller secara manual. Masalah yang muncul meliputi pemborosan energi dan gangguan pada pelayanan medis akibat ketidakstabilan suhu di dalam gedung. Dalam mengatasi permasalahan tersebut, dirancang sebuah sistem melalui penerapan metode sequencing control pada kontrol chiller. Metode ini digunakan untuk mengatur operasional chiller dalam urutan tertentu berdasarkan kebutuhan dan kondisi aktual. Metode ini bertujuan untuk mengoptimalkan penggunaan beberapa unit chiller sehingga efisiensi energi dapat ditingkatkan dan biaya operasional dapat dikurangi. Selain itu, integrasi kontrol chiller dengan Building Automation System (BAS) juga menjadi bagian penting dari rancangan sistem yang dibuat. BAS akan memungkinkan pemantauan real-time terhadap kinerja chiller secara terpusat dan pengambilan keputusan yang lebih cepat dalam menanggapi gangguan teknis. Dengan menggabungkan metode sequencing control dan integrasi dengan BAS, akan membawa dampak positif yang signifikan bagi Rumah Sakit X. Implementasi sequencing control menunjukkan adanya peningkatan performa chiller mencapai 42,2% dengan perubahan nilai COP dari 4,92 menjadi 7 dan efisiensi energi dari 0,7 kW/TR menjadi 0,5 kW/TR. Hal ini membuktikan bahwa sistem yang dirancang menggunakan sequencing control dapat menyesuaikan beban pendingin secara dinamis sesuai kebutuhan aktual rumah sakit, dan chiller bekerja lebih optimal, dengan menggunakan lebih sedikit energi untuk menghasilkan lebih banyak pendinginan. Sistem ini menjadi teknologi yang efektif untuk meningkatkan efisiensi operasional dan mengurangi pemborosan energi di rumah sakit, serta dapat meminimalisir dampak negatif terhadap pelayanan kesehatan di lingkungan rumah sakit.
=================================================================================================================================
Hospital X, a major healthcare center in Surabaya, experienced significant operational challenges related to manual chiller management. The problems include energy wastage and disruption to medical services due to temperature instability in the building. To overcome these problems, a system was designed through the application of sequencing control method in chiller control. This method is used to organize chiller operations in a certain order based on actual needs and conditions. This method aims to optimize the use of multiple chiller units so that energy efficiency can be improved and operational costs can be reduced. In addition, the integration of chiller control with Building Automation System (BAS) is also an important part of the system design. The BAS will enable real-time monitoring of chiller performance centrally and faster decision-making in response to technical faults. By combining the sequencing control method and integration with BAS, it will bring significant positive impacts to Hospital X. The implementation of sequencing control showed an increase in chiller performance of 42,2% with a change in COP value from 4,92 to 7 and energy efficiency from 0,7 kW/TR to 0,5 kW/TR. This proves that the system designed using sequencing control can dynamically adjust the cooling load according to the actual needs of the hospital, and the chiller works more optimally, using less energy to produce more cooling. This system is an effective technology to improve operational efficiency and reduce energy waste in hospitals, and can minimize the negative impact on health services in the hospital environment.
Item Type: | Thesis (Diploma) |
---|---|
Uncontrolled Keywords: | Efisiensi Energi, Kontrol Chiller, Sequencing Control, Chiller Control, Energy Efficiency |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK3070 Automatic control |
Divisions: | Faculty of Vocational > 36304-Automation Electronic Engineering |
Depositing User: | Rakhananta Maulana Ulhaq |
Date Deposited: | 05 Sep 2024 04:26 |
Last Modified: | 05 Sep 2024 04:26 |
URI: | http://repository.its.ac.id/id/eprint/109363 |