Irwanto, Mahardika Rendra (2024) Analisis Kestabilan Transien dan Mekanisme Pelepasan Beban pada PT.Semen Tonasa Akibat Gangguan di PLN dan Pembangkit. Other thesis, Institut Teknologi Sepuluh Nopember.
Text
5022201050-Undergraduate_Thesis.pdf - Accepted Version Restricted to Repository staff only until 1 October 2026. Download (9MB) |
Abstract
Dalam sistem tenaga listrik, menjaga keseimbangan antara kapasitas pembangkitan dan
kebutuhan daya untuk memasok beban adalah salah satu faktor penting dalam menjaga stabilitas
operasional. Stabilitas sistem tenaga dapat berubah sebagai respons terhadap perubahan beban
dan ketersediaan daya. Seringkali, pembangkitan listrik di suatu sistem mengalami gangguan
tak terhindarkan, seperti pemadaman listrik oleh PLN. Ketidakmampuan pembangkit untuk
menyediakan daya biasanya ditandai dengan penurunan frekuensi, dan dalam kasus terburuk,
dapat menyebabkan pemadaman listrik di sistem. Meskipun sistem ini dirancang dengan tingkat
keandalan yang tinggi, kegagalan yang tak dapat dihindari dapat terjadi selama proses
pembangkitan, seperti yang terjadi pada pemadaman listrik di PT. Semen Tonasa yang
menyebabkan generator mengalami beban berlebihan. Kelebihan beban pada generator
mengakibatkan ketidakseimbangan antara daya mekanik yang dihasilkan oleh generator dan
daya listrik yang dikonsumsi oleh beban, sehingga menyebabkan perlambatan rotasi generator.
Pada penelitian ini merekomendasikan pelepasan beban 27.039 MW (metode status) atau
28.014 MW (metode UFR) untuk menjaga stabilitas sistem selama pemadaman PLN. Simulasi
menunjukkan bahwa sistem dapat bertahan dari pemadaman dua generator, tetapi pemadaman
lebih dari dua generator akan melebihi daya langganan. Hubung singkat 70 kV menyebabkan
penurunan tegangan dan sudut rotor yang signifikan, menunjukkan generator keluar dari
sinkronisasi. Starting motor terbesar menyebabkan penurunan tegangan sementara dikarenakan
nilai arus starting yang bernilai 4 x FLA, namun frekuensi tetap aman.
====================================================================================
In the electric power system, maintaining the balance between generation capacity and
power demand to supply the load is one of the critical factors in maintaining operational stability.
The stability of the power system can change in response to load changes and power availability.
Often, electricity generation in a system experiences unavoidable disturbances, such as power
outages by PLN. The inability of the generator to supply power is usually indicated by a
frequency drop, and in the worst case, it can lead to a blackout in the system. Although the
system is designed with a high level of reliability, unavoidable failures can occur during the
generation process, such as the blackout at PT. Semen Tonasa which caused the generator to
experience an overload. Overloading the generator results in an imbalance between the
mechanical power produced by the generator and the electrical power consumed by the load,
causing the generator's rotation to slow down. This study recommends a load shedding of
27.039 MW (status method) or 28.014 MW (UFR method) to maintain system stability during
a PLN blackout. Simulations show that the system can survive the outage of two generators,
but the outage of more than two generators will exceed the subscribed power. A 70 kV short
circuit causes a significant voltage drop and rotor angle, indicating the generator is out of
synchronization. The starting of the largest motor causes a temporary voltage drop due to the
starting current value of 4 x FLA, but the frequency remains safe.
Item Type: | Thesis (Other) |
---|---|
Uncontrolled Keywords: | Power system stability, Load shedding, PT. Semen Tonasa. Kestabilan sistem tenaga, Pelepasan beban, PT. Semen Tonasa. |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1010 Electric power system stability. Electric filters, Passive. |
Divisions: | Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis |
Depositing User: | Mahardika Rendra Irwanto |
Date Deposited: | 31 Jul 2024 01:40 |
Last Modified: | 31 Jul 2024 01:40 |
URI: | http://repository.its.ac.id/id/eprint/109880 |
Actions (login required)
View Item |