Evaluasi Koordinasi Proteksi di PT Semen Indonesia Tuban Plant 1 dengan Mempertimbangkan Arc Flash

Mada, Gusdian Ahmad (2024) Evaluasi Koordinasi Proteksi di PT Semen Indonesia Tuban Plant 1 dengan Mempertimbangkan Arc Flash. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 5022201078-Undergraduate_Thesis.pdf] Text
5022201078-Undergraduate_Thesis.pdf - Accepted Version
Restricted to Repository staff only until 1 October 2026.

Download (7MB) | Request a copy

Abstract

Sistem proteksi tenaga listrik merupakan komponen utama dalam menjaga keandalan dan keamanan operasi sistem listrik. Gangguan seperti arus hubung singkat dapat menyebabkan pelepasan energi dalam bentuk arc flash, yang berpotensi merusak peralatan dan bahkan mengancam keselamatan manusia. Oleh karena itu, penting untuk memahami faktor-faktor yang memengaruhi tingkat bahaya arc flash yang dihasilkan oleh gangguan arus hubung singkat. Permasalahan yang dihadapi adalah bagaimana cara yang tepat dan efektif untuk mengoptimalkan dan mengevaluasi koordinasi proteksi peralatan kelistrikan, lalu untuk mengurangi bahaya yang ditimbulkan oleh terjadinya arc flash saat terjadi gangguan arus hubung singkat dalam sistem tenaga listrik. Dalam penelitian ini digunakan metode evaluasi koordinasi setting waktu pada relai proteksi, khususnya pada Overcurrent Relay. Penelitian ini melibatkan analisis karakteristik sistem tenaga listrik, beban yang terhubung, dan peralatan yang digunakan untuk menentukan pengaturan waktu yang paling efektif. Pengukuran energi arc flash dan waktu respons relai proteksi akan digunakan untuk mengevaluasi kinerja sistem. Selanjutnya dapat diketahui bagaimana penyesuaian setting waktu respons relai proteksi untuk mencapai tingkat keamanan yang optimal tanpa harus mengorbankan kinerja dan keandalan keseluruhan sistem tenaga listrik yang ada di PT Semen Indonesia Pabrik Tuban. Dari hasil evaluasi koordinasi proteksi didapatkan bahwa relai sudah bekerja sesuai standar dan dapat melindungi peralatan utama seperti motor, beban, transformator, dan sumber. Lalu untuk hasil insiden energi pada setiap bus yang disimulasikan didapatkan pada kategori bahaya 3.
=====================================================================================================================================
Electrical power protection systems are a crucial component in maintaining the reliability and safety of electrical system operations. Disturbances such as short-circuit currents can cause the release of energy in the form of arc flash, which has the potential to damage equipment and even threaten human safety. Therefore, it is important to understand the factors that influence the hazard level of arc flash caused by short-circuit currents. The challenge is how to accurately and effectively optimize and evaluate the coordination of electrical equipment protection to reduce the hazards posed by arc flash during short-circuit disturbances in the power system. This research utilizes a method of evaluating time setting coordination on protective relays, particularly Overcurrent Relays. The study involves analyzing the characteristics of the power system, the connected loads, and the equipment used to determine the most effective time settings. Measurements of arc flash energy and protective relay response times will be used to evaluate system performance. The research aims to identify how to adjust the response time settings of protective relays to achieve optimal safety levels without compromising the overall performance and reliability of the power system at PT Semen Indonesia Tuban Plant. From the evaluation of protection coordination, it was found that the relays operated according to standards and were able to protect key equipment such as motors, loads, transformers, and sources. The results of the energy incident simulations for each bus categorized the hazard in category 3.

Item Type: Thesis (Other)
Uncontrolled Keywords: Arus hubung singkat, Relai proteksi, Arc flash, Overcurrent, Short-circuit current, Protection relay
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays. Protective relays--Security measures.
Divisions: Faculty of Intelligent Electrical and Informatics Technology (ELECTICS) > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Gusdian Ahmad Mada
Date Deposited: 30 Jul 2024 07:00
Last Modified: 30 Jul 2024 07:00
URI: http://repository.its.ac.id/id/eprint/109903