Evaluasi Secant Pile Sebagai Perkuatan Dinding Galian Basement Dan Perencanaan Strut-Beam Sebagai Perkuatan Alternatif Studi Kasus: Apartemen Grand Shamaya Surabaya

Salsabila, Ara Zaya (2024) Evaluasi Secant Pile Sebagai Perkuatan Dinding Galian Basement Dan Perencanaan Strut-Beam Sebagai Perkuatan Alternatif Studi Kasus: Apartemen Grand Shamaya Surabaya. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 5012201154-Undergraduate_Thesis.pdf] Text
5012201154-Undergraduate_Thesis.pdf - Accepted Version
Restricted to Repository staff only

Download (5MB) | Request a copy

Abstract

Apartemen Grand Shamaya adalah salah satu apartemen di Surabaya yang merencanakan pembangunan basement sebagai lahan parkir. Basement yang direncanakan terdiri dari 2 lantai yaitu Basement-1 dan Basement-2 dimana elevasi dasar Basement-2 adalah 7 meter di bawah permukaan tanah dasar. Perencanaan struktur basement ini harus stabil dan kuat untuk menahan tekanan horizontal akibat tanah yang kondisinya lunak dan gedung-gedung tinggi di sekitar lokasi proyek. Hasil uji Standard Penetration Test (SPT) menunjukkan bahwa tanah proyek memiliki nilai NSPT kurang dari 1 hingga kedalaman 18 m atau dapat dikategorikan tanah lempung atau lunak. Oleh karena itu, basement pada proyek ini memerlukan dinding penahan tanah yang mampu menahan tekanan lateral yang tersebut.
Apartemen Grand Shamaya menggunakan secant pile sebagai dinding penahan galian basement. Pelaksanaan pekerjaan basement-1 dilakukan dengan sistem bottom-up; tetapi basement-2 dilakukan dengan metode top-down yang dimulai dari Basement-1. Kondisi lokasi proyek yang didominasi oleh tanah lunak menimbulkan kekhawatiran saat pekerjaan galian Basement-1 berlangsung. Oleh karena itu dilakukan evaluasi pada secant pile eksisting untuk menghindari hal-hal yang tidak diinginkan.
Berdasarkan hasil evaluasi dan perencanaan, untuk secant pile eksisting dengan panjang 24 m tidak memenuhi persyaratan karena terjadinya guling akibat momen pendorong yang lebih besar dari momen penahan sehingga dibutuhkan dimensi pile yang lebih panjang. Selain itu, dilakukan penambahan perkuatan strut baja H 300x300 pada secant pile eksisting dengan panjang strut 5 meter dan jarak pemasangan 5 meter. Hasil dari analisis setelah penambahan perkuatan mengalami horizontal displacement sebesar 5,2 mm dengan angka keamanan sebesar 1,65 sehingga dapat memenuhi persyaratan untuk perencanaan perkuatan sementara.
========================================================================================================================
Grand Shamaya Apartment is an apartment in Surabaya that is planning to build a basement as a parking space. The planned basement consists of 2 floors, Basement-1 and Basement-2, where the Basement-2 bottom elevation is 6.8 meters below ground. The design of this basement structure must be stable and strong enough to withstand the horizontal pressure due to the soft soil condition and tall buildings surrounding the project location. The Standard Penetration Test (SPT) results show that the project's soil has NSPT values less than 1 up to a depth of 18 m or can be categorized as clay or soft soil. Therefore, the basement in this project requires a retaining wall that is able to withstand the mentioned lateral pressure.
The Grand Shamaya Apartment uses secant piles as the basement excavation retaining wall. The Basement-1 work is carried out using the bottom-up system; while the Basement-2 uses the top-down method starting from Basement-1. However, during the Basement-1 excavation work, the secant pile experienced deflections with values almost reaching the allowable deflection limit as a retaining wall; this greatly affects the structures around the project location.
Based on the results of the evaluation and planning, the existing 24 m long secant pile does not meet the requirements due to overturning caused by a driving moment greater than the resisting moment, necessitating a longer pile dimension. Additionally, an H 300x300 steel strut reinforcement with a strut length of 5 meters and an installation spacing of 5 meters was added to the existing secant pile. The analysis results after the reinforcement showed a horizontal displacement of 5,2 mm with a safety factor of 1,65 thereby meeting the requirements for temporary reinforcement planning.

Item Type: Thesis (Other)
Uncontrolled Keywords: Basement, Displacement, Secant Pile, Strut, Top-Down
Subjects: T Technology > TA Engineering (General). Civil engineering (General) > TA760+ Retaining walls
Divisions: Faculty of Civil Engineering and Planning > Civil Engineering > 22201-(S1) Undergraduate Thesis
Depositing User: Ara Zaya Salsabila
Date Deposited: 05 Aug 2024 08:37
Last Modified: 05 Aug 2024 08:37
URI: http://repository.its.ac.id/id/eprint/110421