Investigasi dan Mitigasi Pada Performansi Tegangan Sistem Kelistrikan PV on Grid Ketika Terjadi Gangguan

Dieza, Dzacky Aulia (2024) Investigasi dan Mitigasi Pada Performansi Tegangan Sistem Kelistrikan PV on Grid Ketika Terjadi Gangguan. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 5022201093-Undergraduate_Thesis.pdf] Text
5022201093-Undergraduate_Thesis.pdf

Download (7MB)

Abstract

Tren integrasi Pembangkit Listrik Tenaga Surya (PLTS) dengan jaring listrik 3 fasa menimbulkan masalah krusial selama gangguan hubung singkat. Ketika hubung singkat terjadi, hal itu mengakibatkan arus pada bus AC dan tegangan lebih pada bus DC, yang dapat menyebabkan pemutusan sistem tenaga surya dari jaringan. Oleh karena itu, penelitian ini membuat perbaikan penting untuk memenuhi tuntutan regulasi jaringan sistem tenaga. Implementasi strategi kontrol Low Voltage Ride-Through (LVRT) untuk memastikan keandalan sistem fotovoltaik yang terhubung ke jaringan harus disesuaikan dengan kode jaringan masing-masing negara, namun implementasi LVRT yang kompatibel dengan kode jaringan Indonesia masih terbatas. Penelitian ini menyajikan strategi kontrol LVRT yang dimodifikasi berdasarkan kode jaringan Indonesia untuk diimplementasikan dalam sistem yang terhubung ke jaring listrik 25 kV. Modifikasi strategi kontrol LVRT terdiri dari merancang deteksi penurunan tegangan ketika terjadi hubung singkat sebagai referensi injeksi arus reaktif yang sesuai dengan persyaratan kode jaringan Indonesia, dan menggunakan Direct Current Brake Chopper (DC-BC) untuk melindungi DC-link dari tegangan DC berlebihan yang dapat membahayakan inverter.
=================================================================================================================================
The trend of integrating solar power plants with a 3-phase electrical grid poses crucial problems during short circuit disturbances. When a short circuit occurs, it causes overcurrent on the AC bus and overvoltage on the DC bus, which can lead to the disconnection of the solar power system from the grid. Therefore, this research makes crucial improvements to meet the demands of the power system network regulations. Low Voltage Ride-Through (LVRT) control strategy implementation for ensuring the reliability of grid connected photovoltaic system should be adjusted with the grid code of each nation, however the LVRT implementation that compatible with Indonesian grid code is still limited. This paper presents the modified LVRT control strategy based on Indonesian grid code to be implemented in 25 kV grid connected system. The modification of LVRT control strategy consists of designing the voltage sag detection when short-circuit occurred as the reactive current injection reference that suitable with Indonesia grid code requirements and dispatching the Direct Current Brake Chopper (DC-BC) to protect the DC link from excessive DC voltage that can endanger the inverter.

Item Type: Thesis (Other)
Uncontrolled Keywords: PLTS, LVRT, DC-BC, Hubung Singkat, Solar Power Plants, Short Circuit
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1056 Solar power plants. Ocean thermal power plants
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1322.6 Electric power-plants
Divisions: Faculty of Intelligent Electrical and Informatics Technology (ELECTICS) > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Dzacky Aulia Dieza
Date Deposited: 18 Dec 2024 00:58
Last Modified: 18 Dec 2024 00:58
URI: http://repository.its.ac.id/id/eprint/116008