Strategi Peningkatan Efisiensi Energi Pada Sistem Layanan Pompa Booster Gerilya Perusahaan Air Minum Bandarmasih Kota Banjarmasin

Prakoso, Fajar Bayu (2025) Strategi Peningkatan Efisiensi Energi Pada Sistem Layanan Pompa Booster Gerilya Perusahaan Air Minum Bandarmasih Kota Banjarmasin. Masters thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 6014231040-Master_Thesis.pdf] Text
6014231040-Master_Thesis.pdf - Accepted Version
Restricted to Repository staff only until 1 April 2027.

Download (19MB) | Request a copy

Abstract

Biaya energi Perusahaan Air Minum Bandarmasih Kota Banjarmasin pada tahun 2022 adalah sebesar Rp 532/m3 atau sekitar 39% dari total biaya operasional. Biaya energi tersebut masih lebih tinggi dibandingkan dengan rata-rata biaya energi nasional (Rp 356,34/m3). Kondisi topografi tanah di Kota Banjarmasin yang relatif datar menyebabkan pemanfaatan energi potensial (gravitasi) menjadi kurang optimal dalam proses distribusi air minum. Salah satu pompa pada Perusahaan Air Minum Bandarmasih yang menggunakan energi yang cukup tinggi adalah pompa booster Gerilya. Pompa booster Gerilya merupakan pompa distribusi yang mengalirkan air minum ke sebagian zona Banjarmasin Selatan. Total pemakaian listrik pada unit distribusi sistem layanan pompa booster Gerilya pada tahun 2023 adalah sebesar 798.696 kWh.
Tujuan dari penelitian ini adalah untuk menganalisis kelayakan dari rekomendasi peningkatan efisiensi energi ditinjau dari aspek teknis, finansial, dan operasional. Analisis teknis dilakukan dengan melakukan pemodelan pada distribusi jaringan perpipaan menggunakan perangkat lunak EPANET 2.2, analisis finansial dilakukan dengan menghitung Benefit Cost Ratio (BCR), Net Present Value (NPV), Internal Rate of Return (IRR), dan Payback Period (PP) untuk mengetahui kelayakan investasi, serta analisis operasional dilakukan dengan menggunakan analisis SWOT. Rekomendasi peningkatan efisiensi energi yang akan dilakukan antara lain: optimasi pompa, evaluasi headloss pada jaringan perpipaan, dan penerapan elevated reservoir sebagai solusi alternatif penghematan biaya energi. Hasil dari penelitian ini adalah setiap rekomendasi strategi peningkatan efisiensi energi pada sistem layanan pompa booster Gerilya menghasilkan potensi penghematan biaya energi sekitar 200 – 450 juta rupiah per tahun. Penerapan elevated reservoir model 2 memberikan nilai potensi penghematan terbesar yaitu Rp 434.883.265/ tahun, namun jika ditinjau dari aspek finansial tidak memenuhi persyaratan. Ditinjau dari aspek teknis, tekanan pada titik-titik pelanggan pada setiap jam pada semua rekomendasi masih memenuhi persyaratan yaitu minimal 7,5 m. Ditinjau dari aspek finansial, semua rekomendasi memenuhi persyaratan kecuali pada penerapan elevated reservoir model 1 dan model 2. Peningkatan efisiensi pompa merupakan rekomendasi yang memberikan nilai yang paling baik jika ditinjau dari aspek teknis dan aspek finansial. Ditinjau dari aspek operasional, strategi dalam peningkatan efisiensi energi adalah dengan melakukan audit energi secara rutin dan penguatan kelembagaan melalui pelatihan teknis serta peningkatan kualitas rekrutmen pegawai.
=================================================================================================================================
The energy cost of Perusahaan Air Minum Bandarmasih Banjarmasin City in 2022 is Rp 532/m3 or around 39% of the total operational costs. These energy costs are still higher than the average national energy costs (Rp 356.34/m3). One of the causes is the relatively flat topography of the land in Banjarmasin City, which causes the utilization of potential energy (gravity) to be less than optimal in the drinking water distribution process. One of the pumps at Perusahaan Air Minum Bandarmasih that uses quite high energy is the Gerilya booster pump. The Gerilya booster pump is a distribution pump that distributes drinking water to most of the South Banjarmasin zone. The total electricity consumption in the Gerilya booster pump service system distribution unit in 2023 is 798,696 kWh. The purpose of this study is to analyze the feasibility of recommendations for increasing energy efficiency in terms of technical, financial, and operational aspects. Technical analysis is conducted by modeling the distribution of the piping network using EPANET 2.2 software, financial analysis is conducted by calculating the Benefit Cost Ratio (BCR), Net Present Value (NPV), Internal Rate of Return (IRR), and Payback Period (PP) to determine the feasibility of the investment, and operational analysis is conducted by using SWOT analysis. Recommendations for increasing energy efficiency that will be carried out include pump optimization, headloss evaluation on the piping network, and the implementation of elevated reservoir as an alternative solution to save energy costs. The result of the research is that each recommendation of strategy for improving energy efficiency in the Gerilya booster pump service results in potential energy cost savings of around 200 - 450 million rupiah per year. The application of elevated reservoir model 2 provides the largest potential savings value of Rp 434,883,265 / year, but in terms of financial aspects does not meet the requirements. In terms of technical aspects, the pressure at customer points at each hour in all recommendations still meets the requirements of at least 7.5 m. In terms of financial aspects, all recommendations meet the requirements except for the application of elevated reservoir model 1 and model 2. Increasing pump efficiency is a recommendation that provides the best value in terms of technical and financial aspects. In terms of operational aspects, the strategy to improve energy efficiency is to conduct regular energy audits and institutional strengthening with technical trainings for each human resource and improving the quality of employee recruitment.

Item Type: Thesis (Masters)
Uncontrolled Keywords: drinking water, energy efficiency, distribution network, booster pump, air minum, efisiensi energi, jaringan distribusi, pompa booster.
Subjects: T Technology > TD Environmental technology. Sanitary engineering > TD481 Water distribution systems
Divisions: Faculty of Civil, Planning, and Geo Engineering (CIVPLAN) > Environmental Engineering > 25101-(S2) Master Thesis
Depositing User: Fajar Bayu Prakoso
Date Deposited: 23 Jan 2025 01:00
Last Modified: 23 Jan 2025 01:00
URI: http://repository.its.ac.id/id/eprint/116614