Qodir, Musthofa Hasyim Abdul (2025) Pengaruh Kontaminan Hujan Asam Di Permukaan Isolator Polimer Terhadap Karakteristik Tegangan Flashover Dan Arus Bocor Pada Tegangan AC. Other thesis, Institut Teknologi Sepuluh Nopember.
![]() |
Text
5022211205-Undergraduate_Thesis.pdf - Accepted Version Restricted to Repository staff only Download (1MB) | Request a copy |
Abstract
Isolator merupakan salah satu komponen penting dalam sistem transmisi tegangan tinggi yang berfungsi untuk memisahkan konduktor agar tidak mengalirkan suatu arus atau tegangan. Isolator yang digunakan dalam pengujian yaitu isolator polimer dengan jenis pos. Kontaminan hujan asam dan variasi waktu digunakan dalam pengujian ini untuk melihat karakteristik tegangan flashover dan arus bocor yang akan terjadi. Proses pengujian dilakukan dengan menaikkan tegangan tinggi AC pada isolator polimer menggunakan konduktor yang terpasang pada bagian atas isolator polimer yang telah melewati pra-kondisi penyemprotan artificial hujan asam. Isolator polimer disambungan dengan kabel grounding untuk mengukur arus bocor yang terjadi menggunakan clamp meter disaat pengujian hingga terjadinya fenomena flashover. Hasil pengujian yang telah dilakukan berupa nilai tegangan flashover, arus bocor dan arus bocor saat fenomena flashover. Hasil pengujian menunjukkan bahwa kontaminasi larutan artificial hujan asam dengan variasi waktu berpengaruh terhadap penurunan performa isolator. Tegangan flashover menurun dari 62,55 kV pada waktu 0 bulan menjadi 60,793 kV setelah 4 bulan kontaminasi, sedangkan impenasi menurun dari 175,44 MΩ menjadi 166,67 MΩ dan arus bocor saat fenomena flashover meningkat dari 0,396 mA menjadi 0,733 mA. Penelitian ini menunjukkan bahwa kontaminasi artificial hujan asam dengan variasi waktu menunjukkan pengaruh terhadap kondisi permukaan isolator polimer. Hal ini disebabkan oleh kemampuan larutan artificial hujan asam untuk membentuk jalur konduktif pada permukaan serta mempercepat proses degradasi material isolator.
===================================================================================================================================
Insulators are critical components in high-voltage transmission systems, serving to separate conductors and prevent the flow of current or voltage. This study utilized pin-type polymer insulators to investigate the influence of artificial acid rain contamination and varying exposure durations on flashover voltage and leakage current characteristics. The testing procedure involved applying high voltage alternating current (AC) to the polymer insulators via conductors mounted on the upper part of the insulators, which had been preconditioned through artificial acid rain spraying. The insulators were connected to grounding cables, and the leakage current was measured using a clamp meter throughout the testing process until flashover occurred. The test results include flashover voltage values, leakage current, and leakage current during the flashover event. The findings show that contamination from artificial acid rain with varying durations negatively affects insulator performance. Flashover voltage decreased from 62,55 kV at 0 months of exposure to 60,793 kV after 4 months, while impedance dropped from 175.44 MΩ to 166,67 MΩ, and leakage current during flashover increased from 0.396 mA to 0,733 mA. This study concludes that artificial acid rain contamination over time significantly alters the surface condition of polymer insulators by forming conductive paths and accelerating material degradation.
Item Type: | Thesis (Other) |
---|---|
Uncontrolled Keywords: | Arus Bocor, Hujan Asam, Isolator Polimer, Tegangan FlashOver, Tegangan Tinggi AC; Leakage Current, Acid Rain, Polymer Insulators, Flash-Over Voltage, High Voltage AC. |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK3401 Insulation and insulating materials |
Divisions: | Faculty of Intelligent Electrical and Informatics Technology (ELECTICS) > Electrical Engineering > 20201-(S1) Undergraduate Thesis |
Depositing User: | Musthofa Hasyim Abdul Qodir |
Date Deposited: | 25 Jul 2025 02:25 |
Last Modified: | 25 Jul 2025 02:25 |
URI: | http://repository.its.ac.id/id/eprint/121278 |
Actions (login required)
![]() |
View Item |