Desain Dan Implementasi Filter Aktif Terkopel Fotovoltaik Menggunakan Teori p-q Pada Kondisi Tegangan Tidak Ideal

Jauhari, Mohammad (2016) Desain Dan Implementasi Filter Aktif Terkopel Fotovoltaik Menggunakan Teori p-q Pada Kondisi Tegangan Tidak Ideal. Masters thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2215201010-Master_Theses.pdf]
Preview
Text
2215201010-Master_Theses.pdf - Published Version

Download (7MB) | Preview

Abstract

Fenomena harmonisa dalam sistem kelistrikan merupakan permasalahan yang sering terjadi. Oleh karena itu, mitigasi harmonisa perlu diperhatikan agar dampak negatif dari harmonisa dapat dikurangi. Filter aktif harmonisa merupakan salah satu metode yang dapat digunakan untuk mereduksi arus harmonisa. Pada penelitian ini dikembangkan filter aktif terkopel fotovoltaik pada kondisi tegangan tidak ideal. Topologi filter aktif terkopel fotovoltaik terdiri dari Voltage Source Inverter (VSI) dengan sisi tegangan searah Direct Current (DC) diparalel dengan fotovoltaik.
Filter aktif akan menyuplai arus anti harmonisa dan daya reaktif ke jala-jala. Arus anti harmonisa akan digunakan untuk mengeliminasi arus harmonisa pada jala-jala. Fotovoltaik akan menyuplai daya aktif ke jala-jala melalui pengaturan DC-bus VSI. Normalisasi tegangan tidak ideal dilakukan dengan menggunakan Phase Lock Loop (PLL) untuk mendeteksi sudut fasa. sudut fasa ini kemudian digunakan untuk membangkitkan sinyal tegangan tiga fasa. sinyal tegangan tiga fasa hasil normalisi ini kemudian digunakan dalam perhitungan teori p-q untuk membangkitkan arus anti harmonisa dalam kondisi tegangan tidak ideal.
Hasil dari penelitian ini mampu mengurangi kandungan harmonisa, Total Harmonic Distortion (THD), dari 28.34% menjadi 2.26% pada pengujian ratting desain yang digunakan. Pada penelitian ini hasil analisa data menggunakan software Matlab. Dan untuk implementasinya menggunakan mikrokontroler.
=========================================================
=========================================================
The phenomenon of harmonics in electrical systems is a problem that often occurs. Therefore, mitigation of harmonics is necessary so that the negative effects of harmonics can be reduced. Active power filters is one method that can be used to reduce harmonic distortion. In this research, the development of active power filter coupled photovoltaic under nonideal mains voltages. The active power filter topology consists of a Voltage Source Inverter (VSI) arranged in parallel with photovoltaic.
Active power filters will supply anti harmonic currents and reactive power into the grid. Anti harmonic currents will be used to eliminate harmonic currents in the grid. Photovoltaics will supply the active power to grid by controlling the DC-bus VSI. Voltage normalization under nonideal voltage is done using Phase Lock Loop (PLL) to detect the phase angle. The phase angle is then used to generate three-phase voltage signals. The three-phase voltage signal normalization results are then used in the calculation of p-q theory to generate anti harmonic currents under nonideal voltage.
The results of this study were able to reduce the harmonic content, Total Harmonic Distortion (THD), from 28.34% to 2.26% in the test design that used. In this study, the data analysis obtained using Matlab software. And for implementation using microcontroller.

Item Type: Thesis (Masters)
Uncontrolled Keywords: filter aktif terkopel fotovoltaik, Voltage Source Inverter (VSI), teori p-q, tegangan tidak ideal, Phase Lock Loop (PLL), mikrokontroler.
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Faculty of Industrial Technology > Electrical Engineering > 20101-(S2) Master Thesis
Depositing User: MOH. JAUHARI
Date Deposited: 16 Mar 2017 03:54
Last Modified: 16 Mar 2017 03:54
URI: http://repository.its.ac.id/id/eprint/1918

Actions (login required)

View Item View Item