Optimisasi Pengaturan Kompensasi Daya Reaktif Pada Sistem Tenaga Listrik Menggunakan Multi Tipe Facts Devices Berbasis Improved Gravitational Search Algorithm

-, Purwoharjono (2014) Optimisasi Pengaturan Kompensasi Daya Reaktif Pada Sistem Tenaga Listrik Menggunakan Multi Tipe Facts Devices Berbasis Improved Gravitational Search Algorithm. Doctoral thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2210301003-Disertation.pdf] Text
2210301003-Disertation.pdf
Restricted to Repository staff only

Download (2MB) | Request a copy

Abstract

Semakin meningkatnya biaya yang diperlukan untuk membangun saluran
transmisi, pusat pembangkit baru dan meningkatnya kebutuhan penggunaan
barang-barang elektronika daya merupakan alasan penggunaan FACTS device.
FACTS (Flexible AC Transmission System) device merupakan peralatan yang
dapat digunakan untuk mengatur dan meningkatkan aliran daya serta kestabilan
pada sistem tenaga listrik. Penggunaan FACTS device ini dapat digunakan secara
luas pada sistem tenaga listrik, sehingga menjadi lebih fleksibel terhadap
pembangkitan dan beban yang bervariasi. Penelitian ini mengembangkan metode
berbasis kecerdasan buatan untuk mengatur kompensasi daya reaktif
menggunakan multi tipe FACTS device. Metode yang diperbaiki dalam penelitian
ini adalah metode GSA. Metode GSA merupakan metode metaheuristik baru yang
terinspirasi oleh hukum Newton tentang gravitasi dan gerak massa. Perbaikan
metode GSA ini menggunakan LDIW (Linear Decrasing Inertia Weight), FL
(Fuzzy Logic) dan IT2FLS (Interval Type 2 Fuzzy Logic System). Perbaikan
metode GSA ini dilakukan dengan cara menyesuaikan bobot inersia, yang dapat
digunakan untuk mengatur kecepatan partikel pada metode GSA, sehingga dapat
meningkatkan performansi metode GSA. Perbaikan metode GSA ini dinamakan
Improved GSA (IGSA). Jenis FACTS device yang akan digunakan pada
penelitian ini, meliputi: TCSC (Thyristor Controlled Series Capasitor), SVC
(Static Var Compensator) dan TCPST (Thyristor Controlled Phase Shifting
Transformer). Hasil dari IGSA ini disimulasikan pada multi tipe FACTS devices
dan di bagi dalam 5 (lima) model simulasi, yaitu: 1). Simulasi aliran daya sebelum
pemasangan FACTS device, 2). Simulasi aliran daya setelah pemasangan TCSC,
3). Simulasi aliran daya setelah pemasangan SVC, 4). Simulasi aliran daya setelah
pemasangan TCPST dan 5). Simulasi aliran daya setelah pemasangan SVCTCSC-
TCPST. Simulasi dilanjutkan dengan melakukan uji kestabilan tegangan
pada setiap bus yang meliputi uji kestabilan tegangan sebelum pemasangan
FACTS device dan uji kestabilan tegangan setelah pemasangan FACTS device.
Hasil akhir simulasi penelitian ini dapat bermanfaat untuk meminimalkan rugirugi
daya pada saluran transmisi, memperbaiki deviasi tegangan dan
meminimalkan investasi biaya FACTS device, serta bermanfaat untuk
meningkatkan kestabilan tegangan pada sistem tenaga listrik.

====================================================================================

One of the reasons to use FACTS device is the increasing costs required to
build a transmission line, the new power plant and the growing need for the use
of power electronics goods. FACTS device is an equipment used to regulate and
improve power flow and stability in power system. FACTS device can be widely
used in the electric power system so that it becomes more flexible on varying
generation and load. This study developed a method of artificial intelligence to
manage reactive power compensation using a multi type FACTS device. The
method used in this study was the method of improved GSA. GSA method is a
new metaheuristic method inspired by Newton's laws of gravity and mass motion.
Improved GSA uses LDIW (Linear Decrasing Inertia Weight), FL (Fuzzy Logic)
and IT2FLS (Interval Type 2 Fuzzy Logic System). This GSA that is improved is
used to adjust inertia weight used to control the speed of the particles on the GSA
and it is applied to postional change mutation of a new agent so as to improve the
performance of the GSA method. This new GSA method is called Improved GSA
(IGSA). Types of FACTS device used in this study were TCSC (Thyristor
Controlled Series Capacitor), SVC (Static Var Compensator) and TCPST
(Thyristor Controlled Phase Shifting Transformer). The results of the IGSA were
simulated on multi-type FACTS devices and divided in 5 simulation model
namely 1). Power flow simulation before installation of FACTS device, 2). Power
flow simulation after installation of TCSC, 3). Power flow simulation after
installation of SVC, 4). Power flow simulation after installation TCPST and 5).
Power flow simulation after installation of the SVC-TCSC-TCPST. After the
simulation of the results of this IGSA was performed, it was then proceeded with
voltage stability test on each bus that includes voltage stability test before and
after installation FACTS device. Final result of this research simulation can be
useful to minimize power loss in the transmission line, repair the voltage
deviation and minimize FACTS device cost investment as well as beneficial to
improve the voltage stability of the power system.

Item Type: Thesis (Doctoral)
Additional Information: RDE 621.319 Pur o
Uncontrolled Keywords: FACTS device; SVC; TCSC; TCPST; GSA; IGSA
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK5105.546 Computer algorithms
T Technology > TS Manufactures > TS167 Costs, Industrial
Divisions: Faculty of Industrial Technology > Electrical Engineering > 20001-(S3) PhD Thesis
Depositing User: Anis Wulandari
Date Deposited: 23 May 2017 06:28
Last Modified: 27 Dec 2017 02:29
URI: http://repository.its.ac.id/id/eprint/41352