Analisa Termodinamika Pengaruh Aliran Massa Ekstraksi Turbin Uap Bagian High Pressure Untuk Feedwater Heater Terhadap Performa Pembangkit Listrik Tenaga Uap 200 Mw Pt. Pjb Gresik

Simamora, Rizky Yusuf Fernando (2015) Analisa Termodinamika Pengaruh Aliran Massa Ekstraksi Turbin Uap Bagian High Pressure Untuk Feedwater Heater Terhadap Performa Pembangkit Listrik Tenaga Uap 200 Mw Pt. Pjb Gresik. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[img]
Preview
Text
2108100099-undergraduate thesis.pdf - Published Version

Download (2MB) | Preview

Abstract

Salah satu jenis pembangkit yang banyak di gunakan adalah pembangkit listrik tenaga uap (PLTU) yang bekerja dengan siklus Rankine. Salah satu cara meningkatkan effisiensi dari sebuah PLTU adalah dengan menambahkan feedwater heaters (FWH) ke dalam sistem, yang bermaksud meningkatkan temperatur air yang akan dipanaskan di dalam boiler, sehingga uap keluaran dari boiler bias memiliki temperatur yang lebih tinggi dibandingkan tanpa FWH. Energi yang digunakan FWH berasal dari ekstraksi turbin uap, dengan jumlah aliran massa dan tekanan tertentu. Proses ektraksi yang kurang tepat dapat mengakibatkan effisiensi turbin menurun dan dapat mengakibatkan efesiensi pembangkit menurun. Sehingga diperlukan studi lebih lanjut untuk mengetahui komposisi yang tepat pada ekstraksi turbin uap. Penilitian mengenai pengaruh aliran massa dan tekanan ekstraksi turbin uap ini dilakukan dengan perhitungan yang digunakan menggunakan standar ASME PTC 6 untuk Performa Turbin Uap dan. Perhitungan performa pertama dilakukan pada model PLTU 200 MW dengan 3 buah turbin (high pressure, intermediate pressure, dan low pressure) dengan 8 FWH. Metode variasi persentase ekstraksi steam dilakukan berdasarkan standar General Electric yaitu aliran massa untuk FWH1 dan FWH2 yang diambilkan dari ekstrasi uap turbin high pressure divariasikan diawali dengan persentase 5% HPH1 dan 11% HPH2. Kemudian, 6% HPH1 dan 10% HPH2, 8% HPH1 dan 8% HPH2(kondisi eksisting), dan variasi dibalik untuk HPH1 dan HPH2 secara berurutan. Kondisi eksisting PLTU unit tiga PT. PJB Gresik memiliki efisiensi boiler 89.21% , heat rate 8554.15 kJ/kW.hr, dan suhu flue gas adalah 130.29 0C. Pengaruh variasi jumlah ekstraksi aliran massa uap terhadap performa pembangkit adalah apabila ekstraksi uap untuk HPH1 sedikit dan HPH2 banyak berdampak heat rate naik (buruk) karena bahan bakar yang diperlukan lebih banyak untuk memanaskan air menjadi uap walaupun daya yang dihasilkan tinggi, misal variasi ekstraksi 5- 11, dan sebaliknya apabila ekstraksi uap untuk HPH1 banyak dan HPH2 sedikit berdampak heat rate juga naik karena daya yang dihasilkan pembangkit turun, misal variasi 11-5. Oleh karena itu, pemilihan pembangkit berdasarkan nilai heat rate adalah pembangkit dengan ekstraksi 8-8 sebagai pembangkit yang terbaik. ============================================================================================ One of the most type of plant is the steam power plant (PLTU) which works with the rankine cycle. One way to improve the efficiency of the power plant is addedfeedwater heaters (FHW) into the system. So that the steam output of the boiler can have a higher temperature than before. The energy which used by FHW comes from steam turbine with certain mass flow and pressure. Wrong extraction process can decreased turbine efficiency and the result will make the plant efficiency decrease.So that further study is needed to determine the exact composition of the extraction steam turbine. The research about the effect of mass flow and pressure from steam turbine extraction is done by using a standart calculation ASME PTC 6 for steam turbine and the first performance calculation performed on the model plant of 200 MW with three tubines (high pressure, intermediate pressure, and low pressure) with 8 FWH. Percentage variation of steam extraction method is based on standard General Electric mass flow for HPH1and HPH2 were taken from the extraction of high pressure steam turbine varied begins with a percentage of HPH1 5% and HPH2 11%. Then, HPH1 6% and HPH2 10%, HPH1 8% and HPH2 8% (as an existing condition), and the variation is reversed for HPH1 and HPH2 sequentially. The existing condition of power plant unit III PT. PJB Gresik has 89.21% boiler efficiency, heat rate 8554.15 kJ/kW.hr. the flue gas temperature 130.29 oC.The influence of variations in the amount of extraction steam mass flow to the plant's performance in bad condition when steam extraction for HPH1 less then HPH2 so that the impact heat rate will increase because needed more fuel to converting the water become steam eventough its have high power, eg extraction 5-11. Therefore, the best plant is the plant which have extraction value 8-8 because its have the lowest value of heat rate.

Item Type: Thesis (Undergraduate)
Additional Information: RSM 621.402 2 Sim a
Uncontrolled Keywords: Mass Flow,Steam Turbine Extraction, Feedwater Heaters, Plant performance
Subjects: T Technology > TJ Mechanical engineering and machinery
T Technology > TJ Mechanical engineering and machinery > TJ164 Power plants--Design and construction
T Technology > TJ Mechanical engineering and machinery > TJ230 Machine design
Divisions: Faculty of Industrial Technology > Mechanical Engineering > (S1) Undergraduate Theses
Depositing User: Mr. Tondo Indra Nyata
Date Deposited: 08 Jun 2017 05:26
Last Modified: 08 Jun 2017 05:26
URI: http://repository.its.ac.id/id/eprint/41531

Actions (login required)

View Item View Item