Aryanto, Denis (2015) Studi Eksperimental Pengaruh Variasi Temperatur Dan Debit Thermal Oil Sebagai Heater Generator Terhadap Performansi Mesin Pendingin Difusi Absorpsi R22-Dmf. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.
Preview |
Text
2112106042-Undergraduate Thesis.pdf - Published Version Download (4MB) | Preview |
Abstract
Sistem pendingin saat ini sudah menjadi salah satu
kebutuhan yang sangat penting untuk menunjang berbagai
aktifitas manusia seperti kebutuhan dibidang industri,
pendidikan, perumahan dan kebutuhan lainnya. Salah satu
teknologi pendinginan yang ada saat ini adalah sistem refrijerasi
difusi absorpsi atau DAR (Diffusion Absorption Refrigeration).
Sistem ini menggunakan generator untuk menjalankan sistemnya
sebagai pengganti kompresor pada sistem kompresi uap. Berbeda
dengan kompresor, generator membutuhkan input berupa kalor.
Besar kecilnya COP (Coefficient of performance) mesin
pendingin difusi absorpsi salah satunya dipengaruhi oleh jumlah
kalor yang diberikan pada generator. Eksperimen ini bertujuan
untuk melakukan analisa unjuk kerja pada mesin pendingin difusi
absorpsi sehingga performa mesin dapat meningkat.
Eksperimen dilakukan dengan menggunakan mesin
pendingin difusi absorpsi yang berada di jurusan Teknik Mesin
ITS yang telah dimodifikasi pada bagian sumber panas
menggunakan thermal oil sebagai heater generator. Fluida kerja
dalam sistem yang digunakan adalah pasangan refrijeranabsorben
R22-DMF (Dimethylformamida) dengan konsentrasi
massa 60%-40%. Pengambilan data dilakukan dengan 3 variasi
viii
debit thermal oil yaitu : 6 liter/jam, 8 liter/jam, dan 10 liter/jam.
Sedangkan temperatur thermal oil divariasikan sebesar 90ºC,
110ºC dan 130ºC. Dari eksperimen tersebut diperoleh data-data
sebagai acuan perhitungan pengaruh variasi temperatur dan
debit thermal oil terhadap performansi sistem pendingin difusi
absorpsi.
Hasil yang didapatkan dari eksperimen ini adalah unjuk
kerja terbaik dari sistem difusi absorpsi ini diperoleh nilai COP
terbesar 0.612 yang didapatkan pada temperatur thermal oil
sebesar 130ºC dengan debit thermal oil sebesar 8 liter/jam.
Untuk nilai kapasitas pendinginan ) terbesar diperoleh
sebesar 139,1 watt, laju perpindahan panas pada generator
( ) 233 watt, laju perpindahan panas pada kondensor 143
watt, laju alir massa refrijeran 0.000721 kg/s serta efisiensi
generator 0,233 yang didapatkan pada temperatur thermal oil
sebesar 130ºC dan debit 6 liter/jam.
============================================================================================
Refrigeration systems nowadays have become one of the
most important need to support human activities such as
industrial, educational, residential etc. One of the refrigeration
technology that still exist is Diffusion Absorption Refrigeration
(DAR). The system used the generator to start the system as a
substitute for compressor in vapour compression system.
Different with compressor, the generator need amount of heat to
start. Coefficient of performance (COP) of this system mostly
influenced by number of heat that supplied to the generator. This
experiment is used to analyze the performance of diffusion
absorption refrigeration system so the performance can be
improved.
The experiment used diffusion absorption refrigeration
system at mechanical engineering department of ITS that has
modified so it can use thermal oil as heater generator. The
working fluids used in this system are refrigerant-absorbent pair
R22-DMF (Dimethylformamida) with 60%-40% mass
concentration. Data decision did with 3 variations of fluid flow, 6
litre/hour, 8 litre/hour and 10 litre/hour. Thermal oil temperature
varied into 90ºC, 110ºC and 130ºC. From this experiment we
x
gained datas as reference for performance calculation of this
system.
The result that can be obtained from this experiment is the
best performance for this diffusion absorption refrigeration
system gained the highest COP 0.612 from 130ºC thermal oil
temperature and 8 litre/hour fluidflow. It is also obtained that
cooling capacity ( ) is 139,1 watt, heat transfer rate of
generator ( ) is 233 watt, heat transfer rate of condenser
( ) is 143 watt, mass transfer rate of refrigerant is 0.000721
kg/s and generator efficiency is 0,233 that all gained from 130ºC
thermal oil temperature and 6 litre/hour fluidflow
Item Type: | Thesis (Undergraduate) |
---|---|
Additional Information: | RSM 621.56 Ary s |
Uncontrolled Keywords: | Difusi Absorpsi, DAR, COP, R22-DMF, Heater Generator. |
Subjects: | T Technology > TJ Mechanical engineering and machinery > TJ223 PID controllers T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1318 Geothermal Power Plants |
Divisions: | Faculty of Industrial Technology > Mechanical Engineering > 21201-(S1) Undergraduate Thesis |
Depositing User: | Mr. Tondo Indra Nyata |
Date Deposited: | 09 Jun 2017 03:41 |
Last Modified: | 24 Aug 2018 02:04 |
URI: | http://repository.its.ac.id/id/eprint/41557 |
Actions (login required)
View Item |