Desain Filter Pasif Harmonisa pada Sistem Kelistrikan CPA Petrochina Tuban

Fatkhurrohman, Mas (2015) Desain Filter Pasif Harmonisa pada Sistem Kelistrikan CPA Petrochina Tuban. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[img]
Preview
Text
2212105083-undergraduated_thesis.pdf

Download (1MB) | Preview

Abstract

JOB P-PEJ (Joint Operating Body Pertamina – Petrochina East Java), Tuban bergerak dalam bidang produksi minyak dan gas. Central Processing Area (CPA) merupakan suatu tempat untuk proses pemisahan fluida dan gas lebih lanjut. Dalam kegiatan produksinya, plant CPA JOB P-PEJ (Central Processing Area Joint Operating Body Pertamina – Petrochina East Java), Tuban menggunakan berbagai macam peralatan elektronika daya seperti variable speed drive (VSD), lampu fluorescent, dan lain - lain. Efek dari penggunaan alat –alat tersebut yaitu menimbulkan permasalahan kualitas daya (power quality) yaitu berupa munculnya gangguan harmonisa dalam sistem tenaga listrik yaitu pada MCC PAD A THDV 9.63%, BB MCC PAD-B THDV 8.73%, BB MCC PAD C THDV 9.55% dan MCC5.2 THDV 6.49%. selain itu operasi yang digunakan pada Plant CPA saat ini adalah PP1 dan PP2 (yang mengalami penambahan generator Centaur 2 dan 4 motor pump baru) yang bekerja secara independen (konfigurasi belum terintergrasi). Untuk meningkatkan keandalan di plant CPA secara keseluruhan (PP1 dan PP2) maka akan ada wacana PP1 dan PP2 ke depan dioperasikan terintegrasi. Pada tugas akhir ini, software yang digunakan untuk proses simulasi adalah ETAP 7.5 untuk melakukan peredaman harmonisa dengan menggunakan filter pasif yang didesain saat konfigurasi belum terintergrasi. Hasil dari tugas akhir ini menunjukkan bahwa penggunaan filter pasif single tuned yang didesain saat konfigurasi belum terintergrasi dapat mengurangi nilai harmonisa yang ditimbulkan sehingga memenuhi standar IEEE Std. 519-1992 baik untuk konfigurasi belum terintergrasi maupun untuk konfigurasi terintergrasi dalam wacana kedepanya. ================================================================================================================== JOB P-PEJ (Joint Operating Body Pertamina – Petrochina East Java) Tuban operates in production oil and gas industry. Central Processing Area (CPA) is a place to separate between fluid and gas more futher. In the production of process plant CPA JOB P-PEJ(Central Processing Area Joint Operating Body Pertamina – Petrochina East Java), Tuban using the variety of power electronic devices such as variable speed drive (VSD), fluorescent lamp, etc. The effect from using such tools is the presence of power quality namely harmonic distortion. The presence of harmonic is detected in MCC PAD A THDV 9.63%, BB MCC PADB THDV 8.73%, BB MCC PAD C THDV 9.55% and MCC5.2 THDV 6.49%. In addition, the current operating that using by plant CPA is PP1 and PP2(with added generator centaur 2 and 4 pump motor) working independently(configuration not integrated).To improve reliability in plant CPA in a whole(PP1 and PP2), there are some proposes to integrate between PP1 and PP2 in the future. In this final project the software that are using is ETAP 7.5 in order to damp the harmonic with using pasif filter designed when the condition has not been integrated yet. The result of this final project give evidence that the using pasiv filter single tune designed when the condition has not been integrated yet, successfully decrease the harmonic value hence this current condition fulfill standart IEEE Std. 519-1992 for configuration not integrated or the integrated configuration for the purpose of development in the future.

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.319 3 Fat d
Uncontrolled Keywords: filter pasif single tuned, Harmonisa, peningkatan kehandalan, CPA JOB P-PEJ (Central Processing Area Joint Operating Body Pertamina – Petrochina East Java)
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission
T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Faculty of Industrial Technology > Electrical Engineering > (S1) Undergraduate Theses
Depositing User: Mr. Fandika aqsa
Date Deposited: 13 Jun 2017 03:12
Last Modified: 13 Jun 2017 03:12
URI: http://repository.its.ac.id/id/eprint/41619

Actions (login required)

View Item View Item