Simulasi Numerik Pengaruh Kecepatan Inlet Dan Posisi Ketinggian Outlet Terhadap Karakteristik Aliran Dan Perpindahan Panas Konveksi Pada Ruang Server Dengan Floor Inlet Flow

Fasya, Teuku Reza Maulana (2017) Simulasi Numerik Pengaruh Kecepatan Inlet Dan Posisi Ketinggian Outlet Terhadap Karakteristik Aliran Dan Perpindahan Panas Konveksi Pada Ruang Server Dengan Floor Inlet Flow. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2115105017-Undergraduate-Thesis.pdf]
Preview
Text
2115105017-Undergraduate-Thesis.pdf - Published Version

Download (2MB) | Preview

Abstract

Ruang server merupakan ruangan yang digunakan untuk
menyimpan server yang berisi database, perangkat jaringan komputer dan perangkat lainnya yang terkait. Sebuah ruang server harus memiliki tingkat keamanan yang sangat tinggi, salah satunya yang harus sangat diperhatikan adalah suhu pada ruangan dan suhu pada rak dari server. Di dalam server terdapat suatu komponen elektronik yang jika bekerja terus menerus dapat mengakibatkan overheat, bila suatu komponen elektronik overheat dan menjadi rusak maka database yang ada pada server tersebut bisa menjadi hilang. Mengacu pada standar Thermal Guidelines for Data Processing Environments ASHRAE untuk komponen elektronik pada server akan bekerja optimal di bawah temperatur kerja 45˚C, akan tetapi sebagian besar pada ruang server temperatur pada server dijaga agar bekerja kurang dari 40˚C agar komponen elektronik pada server dipastikan bekerja secara aman.
Pada penelitian kali ini suatu ruang server di simulasikan dengan menggunakan CFD (Computating Fluid Dynamic) dengan
aplikasi GAMBIT 2.4.6 untuk pemodelan dari sistem dan aplikasi
ANSYS 16.2 untuk mengetahui perpindahan panas, distribusi temperatur, karakteristik aliran pada rak server. Pemodelan pada penelitian kali ini mengguanakan inlet berjenis floor inlet dengan ke jumlah inlet 16 dan temperatur pada inlet dari 15 ˚C dengan kondisi batas adalah velocity inlet tiap kecepatan dari inlet di variasikan 2m/s; 2,5m/; 3m/s, tiap rak server diberi kondisi batas heat flux konstan sebesar 250 W/m2 sedangkan untuk outlet diberikan kondisi batas outflow dengan variasi ketinggian outlet pada ketinggian 0,5m; 1m; 1,8m; 3m.
Hasil dari simulasi adalah hasil kualitatif berupa visualisasi karakteristik aliran udara dan perpindahan panas pada
server diantaranya adalah distribusi temperatur dan distribusi
kecepatan pada rak server. Selain data kualitatif di dapatkan juga data kuantitatif yang selajutnya di olah menjadi grafik perbandingan antara Nusselt Number, koefisien perpindahan
panas secara konveksi pada rak server yang melebihi batas critical temperture. Kesimpulan pada penelitian kali ini adalah pada kecepatan 2 m/s semua rak server bagian belakang server atau tempat diletakannya sensor, temperatur surface melebihi batas critical temperature 40˚C. Pada kecepatan 2,5 m/s critical temperature hanya terdapat pada temperature surface di rak server 1 pada ketinggian outlet 1,8 m dan pada ketinggian outlet 3 m critical temperature berada pada rak server 8. Sedangkan pada kecepatan inlet 3m/s semua rak server berada pada temperatur yang aman

=================================================================

The server room is a room that is used to store the server
that contains the database, computer network devices, and other related devices. A server room should have a very high level of security, one of which must be very aware is room temperature and the temperature on a rack of servers. The server side there is an electronic component that if working continuously can result in overheating when an electronic component overheats and become damaged then the database existing on the server can be lost. Refers to the standard Thermal Guidelines for Data Processing Environments ASHRAE for electronic components on the server will work optimally under the working temperature of 45 ˚C, but mostly at the server room temperature on a server maintained in order to work less than 40 ˚C so that the electronic components on the server work safely ascertained.
In the present study a server space simulated by using CFD (Computating Fluid Dynamic) with GAMBIT 2.4.6 application for the modeling of systems and applications ANSYS 16.2 to determine
the heat transfer, temperature distribution, flow characteristics at the server rack. Modeling in the present study using inlet type
manifold inlet floor with the number of inlet 16 and the temperature at the inlet of 15 ° C with boundary conditions are velocity inlet each velocity of inlet at varying 2m / s; 2.5m /; 3m / s, each rack
server is given boundary condition heat flux constant at 250 W /

m2 while the outlet given boundary conditions outflow with variation in altitude outlet at a height of 0.5 m; 1 m; 1.8m; 3m.
The results of the simulation are qualitative results visualization characteristics of the airflow and heat transfer on the server include temperature distribution and velocity distribution in
the server rack. In addition to qualitative data also obtained quantitative data which further processed into comparison graph
between Nusselt Number, convection heat transfer coefficient at the rack server that exceeds the temperature of the work or the
critical temperature. The conclusion in the present study is at a speed of 2 m / s all server rack at the back of the server or where the sensors is located, the surface temperature exceeds the critical
temperature limit of 40˚C. At a speed of 2.5 m / s critical
temperature found only in surface temperature on server rack 1 at an height of outlet 1.8 and at a height of outlet 3 m critical
temperature is on the server rack 8. While the speed of inlet 3m / s
all rack servers is at a safe temperature

Item Type: Thesis (Undergraduate)
Additional Information: RSM 621.402 2 Fas s
Uncontrolled Keywords: Ruang Server, Critical Temperatur, Database, CFD, Floor Inlet, Karakteristik aliran, Perpindahan Panas, Distribusi Temperatur, Server Room, Critical Temperatur, Database, CFD, Floor Inlet, Characteristica of the airflow, Heat Transfer, Temperature Distribution
Subjects: T Technology > TJ Mechanical engineering and machinery
Divisions: Faculty of Industrial Technology > Mechanical Engineering > 21201-(S1) Undergraduate Thesis
Depositing User: Fasya Teuku Reza maulana
Date Deposited: 17 Oct 2017 07:38
Last Modified: 06 Mar 2019 04:09
URI: http://repository.its.ac.id/id/eprint/47181

Actions (login required)

View Item View Item