Sasanti, Gita Fitri (2017) Pemodelan dan Optimisasi Safety Instrumented System Pada Kolom Distilasi Berdasarkan Perhitungan Dependability dan Cost. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.
Text
2413100085-Undergraduate_Theses.pdf Restricted to Repository staff only Download (2MB) |
Abstract
Pada tugas akhir ini dilakukan optimisasi desain pada Safety Instrumented system pada kolom distilasi berdasarkan perhitungan dependability dan cost dengan metode algoritma genetik. SIS bertujuan membawa proses ke keadaan aman ketika melampaui batas normal operating condition yang telah ditentukan, atau pelanggaran operasional. Keragaman redundansi diimplementasikan sebagai alokasi redundansi yang akan digunakan. Acuan standar internasional yang digunakan dalam tugas akhir ini adalah IEC 61508. Tujuan utama dari studi ini adalah untuk mendapatkan nilai terendah dari PFDavg, STR dan (LCC). PFDavg dipengaruhi oleh laju kegagalan bahaya yang berimbas pada nilai SIL, STR dipengaruhi oleh laju kegagalan aman yang berdampak pada kerugian produksi Subsistem yang akan digunakan mempunyai tiga pilihan teknologi yang memiliki nilai laju kegagalan bahaya dan aman yang berbeda. Hasil optimisasi terbaik memilih 1oo1 sebagai vote pada semua subsistem dengan teknologi smart transmitter dan aktuator air operated dengan nilai LCC 764.360 USD, PFDavg 4,723x10-02/hour, dan STR 3,591x10-05/hour.
======================================================================
b
s
Abstract
-
This
paper
describes the
optimization of
SIS
at distillation
column
based on
dependability and cost measures
using
genetic
algorithm
.
SIS maintain operating condition in the safe regime when
normal operation over the allowable limits.
Diversity redundancy was
implemented as allocation redundancy. The requirement of
SIS
has been
appointed by international standard, IEC 61508. The objectiv
e of this
study is to achieve the lowest value of LCC that
affected by
PFD
avg
and
STR
value
. PFD
avg
is i
nvolved
by failure rate danger that has an effect to
SIL value meanwhile
,
STR is influenced by failure rate safe that has an
effect to the product losse
s caused
unscheduled
shutdown. The field
instruments subsystems are provided
by utilizing
one of or all
different
technologies. The best
optimization
solution utilize
s
vote 1oo1 for all
subsystem with smart transmitter technology and air operated actuator.
It solution obtained LCC
764.360
USD, PFDavg
4,723
x10
-
02
/hour
, and
STR
3,591
x10
-
05
/hour
.
Item Type: | Thesis (Undergraduate) |
---|---|
Uncontrolled Keywords: | Saftey instrumented System, optimisasi, dependability, cost, kolom distilasi |
Subjects: | T Technology > T Technology (General) > T55 Industrial Safety |
Divisions: | Faculty of Industrial Technology > Physics Engineering > 30201-(S1) Undergraduate Thesis |
Depositing User: | Gita Fitri Sasanti |
Date Deposited: | 24 Oct 2017 01:46 |
Last Modified: | 02 Jan 2018 02:16 |
URI: | http://repository.its.ac.id/id/eprint/47213 |
Actions (login required)
View Item |