Rancang Bangun Mesin Water Chiller Kapasitas 6 KiloWatt

Panjaitan, Samuel (2018) Rancang Bangun Mesin Water Chiller Kapasitas 6 KiloWatt. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2115105022-Undergraduate_Theses.pdf]
Preview
Text
2115105022-Undergraduate_Theses.pdf - Accepted Version

Download (2MB) | Preview

Abstract

Indonesia merupakan negara dengan iklim tropis, sehingga lebih dibutuhkan sistem pendingin daripada sistem pemanas. Sistem pendingin dan pengkondisian udara banyak diaplikasikan dalam kehidupan sehari-hari. Salah satu pengaplikasiannya bisa kita temukan pada gedung-gedung bertingkat seperti mall, rumah sakit dan perkantoran. Karena kebutuhan untuk pendinginan pada gedung-gedung bertingkat jauh lebih besar daripada di rumah-rumah maka gedung-gedung bertingkat umumnya tidak menggunakan AC Split karena akan lebih banyak membutuhkan energi. Oleh karena itu mesin water chiller banyak digunakan karena lebih hemat energi dan sanggup untuk kebutuhan pendinginan untuk gedung-gedung bertingkat tersebut.
Pada tugas akhir ini penelitian yang dilakukan adalah merancang dan membangun mesin water chiller kapasitas 6 kW. Mesin water chiller ini dirancang dengan menggunakan sistem kompresi uap yang menggunakan kompressor, kondensor, katup ekspansi dan evaporator sebagai komponen utama. Untuk mesin ini kompressor yang digunakan adalah kompressor bristol, kondensor tipe Circilar Tube – Continuous fin Compact Heat Exchanger evaporator tipe hellical tube dengan diameter nominal ¼ inch dan pipa kapiler TC-70 sebagai katup ekspansi. Air didinginkan dari suhu 25oC sampai 18oC dan menggunakan pompa untuk mensirkulasi air dengan debit 700 l/jam dan fluida kerja yang digunakan adalah R-22.
Dari penelitian ini hasil yang didapatkan adalah dimensi dari evaporator dan pipa kapiler untuk kapasitas pendinginan 19900 Btu/hr. Dimensi evaporator memiliki panjang 20 meter dengan diameter nominal ¼ inch dan jumlah lilitan 13 buah. Sedangkan untuk pipa kapiler memiliki panjang 2 m dengan diameter dalam 0,07 inch. COP rancangan adalah 2,6 sedangkan COP kondisi aktual yang diperoleh adalah 3,3, nilai HRR rancangan adalah 1,18 dan HRR kondisi aktual adalah 1,27 dengan laju alir massa refrijeran (m ̇_ref ) = 0,025 dan besarnya arus listrik yang dibutuhkan adalah 8,3 A dan volume air yang didinginkan adalah 170 liter. Pengujian dilakukan pada tekanan kerja normal. =========== Indonesia is a country with a tropical climate, so more needed cooling system than heating system. Cooling and air conditioning systems are widely applied in everyday life. One of the applications we can find in high rise buildings such as malls, hospitals and offices. Because the need for refrigeration in multi-storey buildings is much larger than in homes, multi-story buildings generally do not use AC Split because it will require more energy. Therefore, water chiller machine is widely used because it is more energy efficient and able to cooling needs for the high rise buildings.
In this final project the research is to design and build water chiller machine with 6 kW capacity. This water chiller machine is designed using a vapor compression system that uses a compressor, condenser, expansion valve and evaporator as the main component. For this machine the compressor used is a bristol compressor, Circilar Tube type condenser - Continuous fin Compact Heat Exchanger type hellical tube evaporator with ¼ inch diameter and TC-70 capillary tube as expansion valve. Water is cooled from 25 ° C to 18 ° C and uses a pump to circulate water with a 700 l / hr discharge and the working fluid employed is R-22.
From this research the results obtained are the dimensions of evaporator and capillary pipe for cooling capacity of 19900 Btu / hr. Evaporator dimensions have a length of 20 meters with a diameter of ¼ inch and the number of windings 13 pieces. As for the capillary pipe has a length of 2 m with a diameter of 0.07 inch. The COP of the design is 2.6 whereas the actual COP condition obtained is 3.3, the design HRR value is 1.18 and the actual condition HRR is 1.27 with the mass flow rate refrijeran (m ̇_ref) = 0.025 and the magnitude of the required electrical current is 8.3 A and the volume of water cooled is 170 liters. The test is carried out at normal working pressure.

Item Type: Thesis (Undergraduate)
Additional Information: RSM 621.815 Pan r
Uncontrolled Keywords: Water Chiller; Evaporator; Pipa Kapiler; R-22; COP; HRR; Evaporator; Pipa Kapiler
Subjects: T Technology > TJ Mechanical engineering and machinery > TJ164 Power plants--Design and construction
T Technology > TJ Mechanical engineering and machinery > TJ230 Machine design
Divisions: Faculty of Industrial Technology > Mechanical Engineering > 21201-(S1) Undergraduate Thesis
Depositing User: SAMUEL PANJAITAN
Date Deposited: 26 Jan 2018 04:30
Last Modified: 24 Sep 2020 02:52
URI: http://repository.its.ac.id/id/eprint/50508

Actions (login required)

View Item View Item