Analisis Karakteristik Arus Inrush pada Transformator 3 Fasa dengan Leg yang Berbeda Berbasis Eksperimen

Ramadhan, Aditya Wahyu (2018) Analisis Karakteristik Arus Inrush pada Transformator 3 Fasa dengan Leg yang Berbeda Berbasis Eksperimen. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111340000124-Undergraduate_Theses.pdf]
Preview
Text
07111340000124-Undergraduate_Theses.pdf - Accepted Version

Download (5MB) | Preview

Abstract

Fenomena arus inrush merupakan kondisi transformator pada saat pertama kali dihubungkan dengan sumber tegangan dan menghasilkan lonjakan arus yang tinggi. Arus inrush dapat menyebabkan gangguan dan akan mempengaruhi kinerja dan sistem proteksi pada transformator. Tujuan dari studi ini adalah untuk mengetahui karakteristik arus inrush pada transformator tiga fasa dengan besar leg yang berbeda sehingga dapat diketahui pula pengaruh perbedaan besar leg dengan arus inrush yang dihasilkan. Pada studi ini dilakukan pengujian dengan mengambil data arus inrush pada transformator uji 3 fasa 5 kVA tipe inti core konvensional, dengan metode pengukuran berbasis eksperimen. Pengujian pada transformator dilakukan pada saat kondisi transien, yaitu saat transformator melakukan energizing. Pengujian ini dilakukan dengan cara menguji setiap fasa secara bergantian dan menguji ketiga fasa secara bersamaan. Hasil pengujian menunjukkan bahwa fasa S yang memiliki leg paling besar diantara kedua fasa lainnya, menghasilkan arus inrush dan arus no load yang paling tinggi dibandingkan kedua fasa lainnya. Selain itu, pada fasa S menunjukkan kurva magnetisasi inti transformator pada area non-saturasi. Hal ini mempengaruhi karakteristik arus yang dihasilkan transformator. =============== Inrush current is the condition when transformer were firstly injected by voltage source which could lead to spiking current. This phenomenon may lead to disruption on protection system and transformer itself. This study , transformer with different legs were used to find out the inrush current characteristic and the inpact of transformer legs size. 5 kVA-Three phase transformers with conventional core type were experimented in this study to find out the inrush current characteristics. Transformer were tested on transient condition, which is when the transformer were injected by voltage source. Transformer were tested on each phase alternately then it was tested on its three phases simultaneously. The experiment results shown that phase S generated the highest inrush current and no load current than the other phases. This could happen because phase S had the biggest leg among the others. Besides, phase S shown magnetization curve of transformer core on its non-saturation curve, which affected the current characteristic generated by the transformer.

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.314 Ram a-1
Uncontrolled Keywords: arus inrush, eksperimen, transformator 3-fasa, leg berbeda, inrush current, experiment, 3-phase transformer, different leg
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK7872 Electromagnetic Devices
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Aditya Wahyu Ramadhan
Date Deposited: 07 Nov 2018 07:45
Last Modified: 15 Apr 2021 07:53
URI: http://repository.its.ac.id/id/eprint/52664