Pada sistem kelistrikan industri, kontinuitas tenaga listrik harus selalu terjaga agar produksi dapat terus berjalan, terlebih pada industri kimia. Jika sekali saja terjadi blackout maka ada kemungkinan produksi akan gagal dan industri tersebut mengalami kerugian. Oleh karena itu dibutuhkan sistem proteksi tenaga listrik yang terkoordinasi dengan baik untuk mencegah terjadinya miskoordinasi proteksi dan blackout pada sistem. Salah satu peralatan proteksi yang digunakan untuk melindungi sistem dari gangguan adalah rele arus lebih.
Pada rele arus lebih inverse (rele 51), parameter-parameter yang perlu diatur adalah arus pickup, jenis kurva, dan Time Dial Setting (TDS). Ketika terjadi gangguan pada sistem, rele primer harus bekerja dengan cepat dan memiliki Coordination Time Interval (CTI) minimal 0,2 detik dengan rele backup.
Namun pada praktiknya, operator sering kesulitan dalam melakukan setting TDS yang tepat dan terkadang tidak mempertimbangkan daerah saturasi rele sehingga perhitungan menjadi tidak tepat. Oleh karena itu dibutuhkan suatu program untuk memudahkan melakukan setting rele arus lebih inverse sehingga dapat menghemat waktu perhitungan dan mendapatkan setting yang tepat. Pada tugas akhir ini dilakukan perhitungan TDS menggunakan metode Modified Particle Swarm Optimization.
Hasil dari tugas akhir ini adalah sebuah program yang dapat menampilkan setting yang tepat dengan waktu operasi dan CTI yang minimum beserta plot kurva Time Current Characteristic (TCC) untuk memastikan bahwa koordinasi sudah tepat.
=========== In industrial electricity system, the power supply continuity must be able to be maintained, so the production will not be interrupted, especially in a chemical industry. If there is a blackout, the production will be failed and that industry will be suffering a financial lost. From that reason, we need a well coordinated protection system so there will be no miscoordination and blackout in the system.
When we set an inverse overcurrent relay (relay 51), there are some parameters that must be calculated such as : pickup current, curve type, and Time Dial Setting (TDS). When there is a fault in the system, primary relay must be able to isolate the fault quickly with minimum Coordination Time Interval (CTI) value is 0,2 second with the backup relay.
In the practice, the operator often finds a difficulty in calculating the TDS, and sometimes not considering the saturation area of the relay so the calculation is not correct. So, we need a program to calculate the TDS so we will get a correct TDS and reduce the calculating time. In this final project, writer make a program to calculate TDS with Modified Particle Swarm Optimization Method.
The result of this final project is a program that show a correct setting of TDS with a minimum time operation and CTI with plot of Time Current Characteristic (TCC) curve to make sure the coordination is correct.

Item Type: Thesis (Undergraduate)
Uncontrolled Keywords: Modified Particle Swarm Optimization; Rele Arus Lebih; Time Dial Setting; Coordination Time Interval; Modified Particle Swarm Optimization; Inverse Overcurrent Relay; Time Dial Setting; Coordination Time Interval
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays. Protective relays--Security measures.
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Muhammad Guntur Istiqlal
Date Deposited: 20 Jul 2018 06:47
Last Modified: 12 Mar 2021 11:37
URI: http://repository.its.ac.id/id/eprint/52705

Actions (login required)

View Item View Item