Laksono, Januardi Budi (2018) Perhitungan Time Dial Setting Inverse Time Overcurrent Relay Dengan Metode Adaptive Modified Firefly Algorithm Pada Sistem Kelistrikan PT. PERTAMINA RU V Balikpapan. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.
Preview |
Text
07111440000113-Undergraduate_Theses.pdf - Accepted Version Download (3MB) | Preview |
Abstract
Sebuah sistem proteksi yang baik harus dapat mengamankan dan meminimalisir suatu gangguan dengan cepat dan tepat sehingga tidak menimbulkan hal-hal yang tidak diinginkan seperti kerusakan alat yang lebih parah, terhentinya suplai daya, dan bahaya bagi manusia. Untuk mendapatkan sistem proteksi yang lebih handal, maka diperlukan adanya koordinasi proteksi yang menghubungkan satu rele dengan rele yang lain. Saat terjadi suatu gangguan dalam sistem tenaga listrik, circuit breaker harus dapat mengamankan gangguan dengan cara membuka. Urutan terbukanya circuit breaker yang benar adalah diawali dengan circuit breaker yang paling dekat dengan sumber gangguan dan diteruskan dengan circuit breaker backup. Hal penting yang harus diperhatikan dari koordinasi proteksi khususnya pada rele arus lebih adalah pengisian parameter TDS (Time Dial Setting). TDS mengatur waktu operasi rele dalam mengamankan suatu gangguan. Umumnya nilai TDS ditentukan menggunakan perhitungan manual untuk mendapatkan nilai TDS minimum. Namun untuk mendapatkan nilai TDS yang tepat dalam pengkoordinasian dengan rele lain masih menggunakan metode trial and error yaitu dengan menggeser kurva sampai mendapatkan nilai CTI yang dirasa tepat, seperti yang terjadi pada sistem kelistrikan di PT. Pertamina RU V Balikpapan. Untuk memudahkan dan mendapatkan hasil TDS yang tepat maka dapat digunakan suatu algorithma khusus. Pada tugas akhir ini akan dibahas tentang cara perhitungan time dial setting inverse time overcurrent relay dengan metode adaptive modified firefly algorithm pada sistem kelistrikan di PT. Pertamina RU V Balikpapan untuk mendapatkan nilai TDS yang minimum. Hasil dari tugas akhir ini adalah mendapatkan nilai TDS minimum pada beberapa jenis tipikal, rata rata waktu operasi rele ketika menjadi rele utama adalah 0,213 detik dan rata rata perhitungan akan konvergen pada iterasi ke 7,2. ========== A good protection system must be able to secure and minimize a disturbance quickly and precisely so there is not undesirable things such as more severe equipment damage, cessation of power supply, and danger to humans. To get a more reliable protection system, it is necessary to coordinate the protection that connects one relay with another relay. In
the event of an interruption in the electrical system, the circuit breaker must be able to secure interference by opening. The exact opening order of the circuit breaker
is preceded by the circuit breaker closest to the fault
source and forwarded by the circuit breaker backups. The important thing to note from the coordination of protection, especially on the relay current is filling TDS (Time Dial Setting)parameters. TDS sets the relay
operation time in securing an interruption. Generally
TDS value is determined using manual calculation to get minimum TDS value. But to get the correct TDS value in coordinating with other relay still use the method of trial and error by shifting the curve until it gets a proper CTI value, as happened to the electrical system at PT. Pertamina RU V Balikpapan. To facilitate and get the right TDS results can be used a special algorithm. In this final project will be discussed a
bout how to calculate time dial setting inverse time overcurrent relay with adaptive modified firefly algorithm method on electrical system at PT. Pertamina
RU V Balikpapan to get minimum TDS value. The results of this final project is to get the minimum v
alue of TDS on some kind of typical, average operating time of the relay when it became the main relay is 0.213 seconds, and average calculation will be convergen on iteration to 7.2.
Item Type: | Thesis (Undergraduate) |
---|---|
Uncontrolled Keywords: | koordinasi proteksi, time dial setting, adaptive modified firefly algorithm, coordination protection, time dial setting, adaptive modified firefly algorithm |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays. Protective relays--Security measures. |
Divisions: | Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis |
Depositing User: | Januardi Budi Laksono |
Date Deposited: | 05 Nov 2018 01:51 |
Last Modified: | 15 Apr 2021 04:59 |
URI: | http://repository.its.ac.id/id/eprint/52784 |
Actions (login required)
View Item |