Rahardjo, Cheryko Adimas (2018) Potensi Penggunaan Kembali Air Buangan AC, Air Hujan, Dan Air Bekas Wudhu Di Lingkungan KampusAMPUS PENS Dan PPNS. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.
Preview |
Text
03211440000105-Undergraduate_Theses.pdf - Accepted Version Download (9MB) | Preview |
Abstract
Kebutuhan sanitasi merupakan aspek yang penting dalam kehidupan. Salah satu bagiannya yaitu kebutuhan air bersih. Di bumi hanya sekitar 3% air bersih yang siap dikonsumsi, maka dari itu memanfaatkan dan mengolah kembali air buangan serta menampung air hujan merupakan salah satu cara mengatasinya. Dalam praktiknya pada kehidupan sehari-hari di Kampus hal tersebut memiliki keuntungan dalam segi finansial dibandingkan dengan penggunaan terus menerus air PDAM. Kampus Politeknik Elektronika Negeri Surabaya (PENS) dan Politeknik Perkapalan Negeri Surabaya (PPNS) memiliki potensi dalam pemanfaatan air buangannya sebagai pengganti air PDAM. Potensi tersebut ditinjau berdasarkan hasil analisis kualitas air dan kuantitas airnya. Air buangan yang berpotensi untuk dijadikan sebagai pengganti air PDAM dengan pengelolaan yang sederhana yaitu air buangan AC, air hujan, dan air bekas wudhu. Analisis potensi ini akan dijadikan acuan sebagai upaya dalam menurunkan biaya yang dikeluarkan untuk pemenuhan kebutuhan air minum Kampus.
Penelitian lapangan ini diawali dengan perumusan ide studi untuk menggunakan kembali air buangan sebagai pemenuhan kebutuhan air bersih di kampus PENS dan PPNS. Aspek-aspek yang dipertimbangkan dalam kajian ini terdiri dari aspek teknis dan finansial. Aspek teknis yang dipertimbangkan berupa kuantitas air buangan, kualitas air buangan, perencanaan teknis penyaluran, pengolahan, penampungan, dan operasional serta perawatannya. Aspek finansial berupa pengeluaran biaya untuk pemenuhan air bersih, biaya pengehamatan pelaksanaan program, biaya investasi konstruksi, dan biaya operasional dan perawatan. Data yang terkumpul dianalisis secara teknis dan kelayakan finansial. Standar yang digunakan yaitu parameter wajib dalam PERMENKES no. 492 tahun 2010.
Dari hasil analisis, menunjukkan melalui penggunaan kembali air bekas wudhu, air buangan AC, dan air hujan pada Kampus PENS dapat dilakukan penghematan sebesar 76% dari total kebutuhan air per tahunnya, yaitu sekitar 36.015 m3 per tahunnya. Sedangkan pada Kampus PPNS, mampu terpenuhi secara 100%, sekitar 47.811 m3 mampu menjadi supply air bersih. Biaya pengeluaran penyediaan air bersih Kampus PENS pada tahun 2017 sejumlah 355 juta rupiah, dapat dilakukan penghematan sebesar 270 juta. Sedangkan pada Kampus PPNS dengan pengeluaran 34,5 juta rupiah pada pengeluaran penyediaan air minum dapat sepenuhnya terbebas dari biaya. Sedangkan, hasil analisis kelayakan finansial pada pengaplikasian program di gedung Pascasarjana Kampus PENS menyatakan bahwa proyek ini layak dilaksanakan secara finansial. Nilai kelayakan finansial program dibuktikan melaluii perhitungan NPV yang menunjukkan nilai 53 juta rupiah dan BCR 1,371.
=============================================================================================================
Sanitation needs are important aspect of life. One of them is the need for clean water. In earth, there is only about 3% of clean water is ready to be consumed, so using and re-processing wastewater and accommodate rain water is one of many ways to overcome it. Practically in daily campus life, it has an economic advantage compared to the using PDAM water continuously. Electronics Engineering Polytechnic Institute of Surabaya (EEPIS) and Shipbuilding Institute of Polytechnic Surabaya (SHIPS) have potential value in reusing of wastewater as a replacement for PDAM water. The potential is reviewed based on the results of water quality and water quantity analysis. Wastewater which used as a replacement for PDAM water with a simple treatment are air conditioning, rain water, and ablution wastewater. This potential analysis will be used as a reference in reducing the costs incurred to fulfill the clean water needs of the Campus.
This research begins with the formulation of the idea of study to reusing wastewater as the fulfillment of clean water needs in EEPIS campus and SHIPS. Aspects considered in this study consist of both technical and financial aspects. Technical aspects considered of wastewater quantity, waste water quality, technical planning of distribution, processing, storaging, and operation and maintenance. Financial aspects include expenditures for clean water fulfillment, program implementation costs, construction investment costs, and operational and maintenance costs. The collected data is both technically and finance feasibility analyzed. Standard parameters used is mandatory requirements in Regulation of Minister of Health No. 492/2010.
From the results of the analysis, shows through the reusing of air conditioning, rain, and ablution wastewater on EEPIS can be savings up to 83% of the total water needs per year, which is about
36.015 m3 per year. While on SHIPS, can be fulfilled 100%, about 47.811 m3 able to become clean water supply. The cost of water supply of EEPIS in 2017 amounting to 355 million rupiah, savings of 270 million rupiah. While on SHIPS with 34,5 million rupiah on the expenditure of drinking water supply, can be entirely free. Meanwhile, the result of financial feasibility analysis on the application of the program in Postgraduate Building of EEPIS stated that the project is feasible to be implemented financially. The financial feasibility of the program is proven through NPV calculation showing the value of 53 million rupiah and BCR 1,371.
Item Type: | Thesis (Undergraduate) |
---|---|
Additional Information: | RSL 628.36 Rah p 3100018075973 |
Uncontrolled Keywords: | Air Hujan, Air Kondensasi AC, Air Wudhu, PENS, PPNS, Ablution Water, Condensed Water, Rainwater Harvesting |
Subjects: | T Technology > TD Environmental technology. Sanitary engineering > TD259.2 Drinking water. Water quality T Technology > TD Environmental technology. Sanitary engineering > TD375 Turbidity--Measurement. T Technology > TD Environmental technology. Sanitary engineering > TD395 Reservoirs (water supply) T Technology > TD Environmental technology. Sanitary engineering > TD418 Water harvesting |
Divisions: | Faculty of Civil, Environmental, and Geo Engineering > Environmental Engineering > 25201-(S1) Undergraduate Theses |
Depositing User: | Rahardjo Cheryko Adimas |
Date Deposited: | 07 Feb 2019 03:42 |
Last Modified: | 23 Oct 2020 07:02 |
URI: | http://repository.its.ac.id/id/eprint/53532 |
Actions (login required)
View Item |