Sistem Monitoring Kecepatan Putar Turbin dan Tegangan Keluaran Generator pada Pembangkit Listrik Tenaga Mini-Mikrohidro Skala Laboratorium

Sari, Delima Palwa (2018) Sistem Monitoring Kecepatan Putar Turbin dan Tegangan Keluaran Generator pada Pembangkit Listrik Tenaga Mini-Mikrohidro Skala Laboratorium. Diploma thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 10511500000005 - Non_Degree.pdf]
Preview
Text
10511500000005 - Non_Degree.pdf - Accepted Version

Download (5MB) | Preview

Abstract

Energi listrik merupakan faktor yang penting dalam kehidupan. Hampir seluruh aktivitas yang dilakukan manusia membutuhkan listrik. Pembangkit listrik tenaga mikrohidro (PLTMH) diciptakan untuk memenuhi kebutuhan kekurangan listrik tersebut. Pada sistem ini air dialirkan menggunakan pompa untuk menggerakan turbin dan menghasilkan mekanik. Energi mekanik tersebut akan diubah menjadi energi listrik oleh generator. Tegangan yang diinginkan sebesar 38 volt untuk menghidupkan lampu, tetapi tegangan yang dihasilkan generator tidak selalu sesuai dengan yang diinginkan. Oleh karena itu, dirancang sebuah sistem monitoring untuk mengetahui kecepatan putar turbin serta tegangan yang dihasilkan generator. Pada perancangan sistem monitoring ini, sensor yang digunakan untuk mengukur kecepatan putar turbin adalah sensor Proximity Hall Effect NJK500-2A. Sedangkan sensor yang digunakan untuk mengukur tegangan keluaran generator adalah sensor Tegangan yang menggunakan modul pembagi tegangan. Dari data uji sistem monitoring didapat hasil yaitu sensor Tegangan memiliki nilai ketidakpastian diperluas (Uexp) sebesar ±0.54 dengan akurasi sebesar 99.81%, dan error pembacaan sebesar 0.19%, sensitivitas sebesar 98,5% serta non linierirtas sebesar 10.186%. Sensor Proximity Hall Effect NJK-5002A memiliki nilai ketidakpastian diperluas (Uexp) sebesar ±12.325 dengan akurasi sebesar 95.39%, dan sensitivitas sebesar 97,56% serta non linierirtas sebesar 7.49%.
========================================================================================================== Electrical energy is an important factor in life. Almost all human activities require electricity. Microhydro power plant (PLTMH) was created to aswer the need for electricity . In this system water flowed using a pump to drive the turbine and produce mechanics energy. The mechanical energy will be converted into electrical energy by the generator. The desired voltage is 38 volts to turn on the lamp, but the generator prodiuced the voltage does not always match with the desired one. Therefore, designed a monitoring system to determine the turbine's speed and generator's output voltage. In designing this monitoring system, the sensor used to measure the turbine's speed is Proximity Hall Effect NJK500-2A sensor. While the sensor used to measure the generator's output voltage is voltage sensor that uses voltage divider module. From the test data of the monitoring system, the result is that the Voltage sensor has an expanded uncertainty value of ± 0.54 with an accuracy of 99.81%, and error reading of 0.19%, sensitivity of 98.5% and non linearity of 10.186%. Proximity Hall Effect NJK-5002A has an expanded uncertainty value of ± 12,325 with an accuracy of 95.39%, and a sensitivity of 97.56% and non linearity of 7.49%.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: kecepatan putar turbin, tegangan, generator, Proximity Hall Effect NJK500-2A , sensor Tegangan.
Subjects: T Technology > T Technology (General) > T57.5 Data Processing
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1001 Production of electric energy or power
Divisions: Faculty of Vocational > Instrumentation Engineering
Depositing User: Delima Palwa Sari
Date Deposited: 09 Jul 2021 09:48
Last Modified: 09 Jul 2021 09:48
URI: http://repository.its.ac.id/id/eprint/57153