Telemetering Pengukuran Tegangan Dan Arus Pada Pengaman Beban Lebih Panel Kontrol Gardu Induk Dengan Komunikasi Wifi

Pratiwi, Wulan Adi (2018) Telemetering Pengukuran Tegangan Dan Arus Pada Pengaman Beban Lebih Panel Kontrol Gardu Induk Dengan Komunikasi Wifi. Diploma thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 10311500010013-Non_Degree.pdf]
Preview
Text
10311500010013-Non_Degree.pdf - Accepted Version

Download (3MB) | Preview

Abstract

Dalam operasinya, salah satu gangguan yang sering terjadi adalah gangguan arus lebih, yang disebabkan oleh kelebihan beban (overload) pada penyulang. Gangguan ini bahkan dapat menyebabkan pemad-aman total (black out) pada GI jika pemutus tenaga (PMT) sisi incom-ing-nya lepas (trip). Dalam sistem operasional, belum tersedia peman-tauan secara telemetering untuk memantau tegangan dan arus pada pengaman beban lebih panel kontrol gardu induk.
Berdasarkan uraian tersebut, maka proses pemantauan tegangan dan arus secara telemetering diawali dengan pembacaan nilai arus dan tegangan menggunakan sensor arus ACS712 dan sensor tegangan ZMPT 101B, kemudian pembuatan front panel LabView untuk membuat tampilan HMI, serta menyesuaikan alamat IP dan port yang telah ditentukan. Selanjutnya membuat program komunikasi wifi menggunakan Ethernet Shield dan access point agar proses telemetering dapat berjalan melalui HMI yang telah dibuat pada pc/laptop.
Hasil yang diperoleh adalah pembacaan sensor arus, nilai %error terkecil terdapat pada fasa T dengan nyala lampu 1 sebesar 0,00440529%. Dan pembacaan sensor tegangan, nilai %error terkecil terdapat pada fasa R sebesar 0,0269058%. Proses pengiriman data secara telemetering dapat berjalan saat %loss sebesar 0% yang dilakukan saat dengan adanya penghalang maupun tanpa adanya penghalang. Sedangkan proses pengiriman data secara telemetering mulai terganggu saat %loss mencapai 50% sampai 100% sehingga proses pemantauan data pengukuran pada panel kontrol gardu induk menggunakan HMI LabView menjadi berhenti.
==============================================================================================
In operation, one of the most problem is the overload problem, which is caused by overload on the feeder. This problem can even cause a blackout of substation if the incoming of breaker (PMT) is off (trip). In operational systems, telemetry monitoring is not yet available to monitor voltage and current on the safety overloads of substation control panels.
Based on the description, voltage and current monitoring process by telemetery begins by measurement of current and voltage values using ACS712 current sensors and ZMPT101B voltage sensors, then manufac-turing LabView front panel to create HMI views, and adjusting the speci-fied IP address and port. Next create a wifi communication program using Ethernet Shield and access point so the telemetry process can run through HMI which has been made on pc / laptop.
The results are current sensor readings, the smallest %error value is in T phase with 1 lamp of 0.00440529%,. And the voltage sensor read-ing, the smallest %error value is in the R phase of 0.0269058%. Telemetry data transmission process can run when the %loss is 0% either done in the presence of obstacles or without any obstacles. While telemetry data transmission start disturbed when the %loss reaches 50% to 100% so the monitoring process of data measurement on the substation control panel using HMI LabView will stop.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Telemetry, Substation, Control Panel
Subjects: T Technology > TJ Mechanical engineering and machinery > TJ213 Automatic control.
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK7872 Electric current converters, Electric inverters.
Divisions: Faculty of Vocational > 36304-Automation Electronic Engineering
Depositing User: Wulan Adi Pratiwi
Date Deposited: 18 Jul 2021 23:26
Last Modified: 21 Jul 2021 23:12
URI: http://repository.its.ac.id/id/eprint/57424