Amania, Radhyana Alamah (2015) Deteksi Lokasi Gangguan Pada Jaringan Distribusi Dengan Percabagangan Menggunakan Metode Gelombang Berjalan. Undergraduate thesis, Institut Technology Sepuluh Nopember.
Preview |
Text
2212106082-Undergraduate Thesis.pdf - Published Version Download (2MB) | Preview |
Abstract
Pada beberapa kasus di sistem distribusi, gangguan sering kali
terjadi dan lokasi gangguan sulit untuk dideteksi. Dibutuhkan waktu
yang cukup lama untuk menemukan lokasi titik gangguan tersebut. Pada
tugas akhir ini, dilakukan perhitungan lokasi titik gangguan
menggunakan gelombang berjalan untuk mempercepat proses perbaikan
setelah gangguan. Pada saluran distribusi, besarnya arus gangguan dapat
mengindikasikan lokasi terjadinya gangguan, hal ini dapat dianalisa
melalui perambatan sinyal arus balik saat terjadi gangguan. Gelombang
akan merambat menyebar ke kedua arah ujung saluran dengan kecepatan
mendekati kecepatan cahaya. Ketika terjadi gangguan inilah tegangan
dan arus titik gangguan tiba-tiba menurun sampai ke nilai rendah.
Perubahan secara tiba-tiba ini yang menghasilkan dorongan energi
elektromagnetik frekuensi tinggi. Perhitungan estimasi lokasi gangguan
secara umum dilakukan dengan menghitung selisih waktu tunda antara
gelombang arus datang (maju) yaitu puncak pertama saat terjadi
gangguan dan gelombang arus refleksinya yaitu puncak gelombang
berikutnya yang di deteksi sebagai arus mundur nya. Dari penelitian ini
diperoleh eror terbesar 8.75 %.
======================================================================================================
In some cases in the distribution system, disturbances often
occur and fault location is difficult to detect. It takes a long time to find
the location of the fault point. In this thesis, the location calculation
using the interruption point wave to accelerate the repair process after
disturbance. By using traveling wave method, used analysis of high
frequency voltages and currents in the distribution system. Waves will
propagate spread to both ends of the channel direction at speeds
approaching the speed of light. When this interference voltage and
current interruption point suddenly falls to a low value. Sudden change
is that generate high-frequency electromagnetic energy boost.
Calculation of fault location estimation is generally done by calculating
the difference in time delay between the current wave coming (forward)
ie when the first peak current wave interference and reflection are the
next wave crest in detection as its backward flow.
Item Type: | Thesis (Undergraduate) |
---|---|
Additional Information: | RSE 621.319 Ama d |
Uncontrolled Keywords: | Gangguan Hubung singkat, Gelombang Berjalan, Sistem Distribusi |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission |
Divisions: | Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis |
Depositing User: | Mr. Tondo Indra Nyata |
Date Deposited: | 16 Aug 2018 03:33 |
Last Modified: | 16 Aug 2018 03:33 |
URI: | http://repository.its.ac.id/id/eprint/59387 |