Penggunaan Kurva Batas Energi Untuk Penyederhanaan Analisis Bahaya Busur Api Pada Sistem Kelistrikan PT. Pupuk Kujang

Rasyd, Ghiffari Al (2019) Penggunaan Kurva Batas Energi Untuk Penyederhanaan Analisis Bahaya Busur Api Pada Sistem Kelistrikan PT. Pupuk Kujang. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111540000109-Undergraduate_Theses .pdf]
Preview
Text
07111540000109-Undergraduate_Theses .pdf

Download (7MB) | Preview

Abstract

Busur api merupakan salah satu faktor yang sangat diperhatikan pada suatu sistem kelistrikan sehingga perlu dilakukan analisis untuk menjamin keselamatan pekerja dari paparan energi insiden yang terpancarkan. Metode dengan standar IEEE 1548-2002 dapat digunakan dalam melakukan analisis bahaya busur api serta dapat menentukan persyaratan dari pakaian pelindung bagi pekerja atau Personal Protective Equipment (PPE). Namun, bila digunakan pada sistem kelistrikan dengan banyak bus, maka memerlukan banyak data dan waktu yang lama dalam menentukan kategori PPE. Metode kurva batas energi digunakan pada tugas akhir ini untuk menyederhanakan analisis. Metode ini merupakan penyederhanaan yang mengacu pada standar IEEE 1584-2002. Hasil dari perpotongan kurva batas energi dengan kurva karakteristik dari pengaman arus lebih atau Overcurrent Protective Device (OCPD) suatu bus yang dianalisis adalah penentuan PPE yang sesuai dengan ketentuan NFPA 70E-2015 serta perhitungan jarak batas aman maksimum busur api. Studi aktual mengenai penyederhanaan analisis bahaya busur api dilakukan pada PT. Pupuk Kujang. Hasil akhir dari analisis adalah dengan menggunakan metode kurva batas energi pada tiap bus dapat menentukan kategori PPE yang tepat dan lebih cepat dibandingkan dengan metode dengan standar IEEE 1548-2002, namun akan timbul perbedaan pada penentuan jarak batas aman busur api. Pada bus 2002-K hasil resetting dengan PPE kategori 3 yang telah ditunjukkan oleh kedua metode, namun dengan jarak batas perlindungan sejauh 16,624 meter untuk metode standar IEEE 1584-2002 dan jarak batas perlindungan maksimum sejauh 20,625 meter untuk metode kurva batas energi.
================================================================================

Arc flash is one of many factors that is very concerned in electrical power system so the analysis is necessary to ensure the safety of workers from being exposed by incident energy emitted. The IEEE 1548-2002 standard method can be used in conducting arc flash hazard analysis and requirements from personal protective equipment (PPE) can be determined. However, if it is used in electrical power systems with many buses, it requires a lot of data and a long time to determine the PPE category. The energy boundary curve method is used in this final project to simplify the analysis. This method is a simplification from IEEE 1584- 2002 standard. The result of the intersection of energy boundary curves with characteristic curves of overcurrent protective devices (OCPD) of a bus that is analyzed is the determination of PPE in accordance with the provisions of NFPA 70E-2015 and the calculation of the maximum distance of the arc flash protection boundary that can protect workers from arc flash. The actual study on simplification of arc flash analysis is carried out at PT. Pupuk Kujang. The final result of the analysis is that by using the energy boundary curve method can determine the right PPE category which is faster than the IEEE 1584 - 2002 standard method. However, there are differences in determining the arc flash protection boundary for each method. On bus 2002-K, the results of resetting with PPE category 3 were shown by the two methods, but with arc flash protection boundary of 16,624 meters for the IEEE 1584-2002 standard method and maximum protection

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.317 Ras p
Uncontrolled Keywords: busur api, standar IEEE 1584–2002, kurva batas energi, personal protective equipment, NFPA 70E-2015
Subjects: T Technology > T Technology (General) > T55 Industrial Safety
T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis