Analisis Pengaruh Kontaminan Terhadap Tegangan Tembus Minyak Isolasi Transformator Dengan Perubahan Variabel Temperatur Minyak

Saputra, Refky Tri (2019) Analisis Pengaruh Kontaminan Terhadap Tegangan Tembus Minyak Isolasi Transformator Dengan Perubahan Variabel Temperatur Minyak. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111540000060-Undergraduate_Theses.pdf] Text
07111540000060-Undergraduate_Theses.pdf - Accepted Version
Restricted to Repository staff only

Download (2MB) | Request a copy

Abstract

Penggunaan minyak isolasi transformator dalam jangka waktu yang lama dan dengan temperatur yang berubah-ubah dapat menimbulkan kontaminan yang mempengaruhi kinerja transformator tersebut. Kontaminan yang terdapat pada transformator jika dibiarkan akan mempengaruhi performa serta mempercepat umur sebuah transformator. Oleh karena itu, maka dilakukan penelitian untuk mengetahui pengaruh kontaminan terhadap tegangan tembus minyak isolasi dengan perubahan temperatur minyak berdasarkan standar uji IEC 156 yang menggunakan dua elektroda setengah bola dengan jarak sela 2,5 mm. Dari hasil pengujian didapatkan hasil bahwa ukuran kontaminan yang berupa kertas isolasi memiliki pengaruh terhadap tegangan tembus minyak isolasi. Semakin kecil ukuran kontaminan maka semakin mudah tertarik medan magnet yang terdapat pada elektroda sehingga menyebabkan terjadinya tegangan tembus. Selain itu, perubahan temperatur juga memiliki pengaruh terhadap besarnya tegangan tembus minyak karena setelah dilakukan pemanasan maka kadar air pada minyak akan berkurang sehingga menyebabkan nilai tegangan tembus pada minyak semakin besar.
================================================================================================
The use of transformer insulating oil for a long time and with varying temperatures can cause contaminants that affect the peformance of the transformer. The contaminants contained in the transformer if left unchecked will affect performance and accelerate the life of a transformer. Therefore, a study was conducted to determine the effect of contaminants on the breakdown of insulating oil with changes in oil temperature based on the IEC 156 standard which uses two half-ball electrodes with a gap of 2,5mm. From the test results it was found that the size of contaminants in the form of insulation paper had an influence on the breakdown of the insulating oil. The smaller the size of the contaminant, the easier it is to be attracted to the magnetic field contained in the electrode, causing breakdown voltage. In addition, changes in temperature also have an influence on the magnitude of the breakdown oil pressure because after heating, the water content in the oil will decrease so that the value of the breakdown voltage in the oil will increase.

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.314 Sap o
Uncontrolled Keywords: Kontaminan, Minyak Isolasi, Tegangan Tembus, Temperatur
Subjects: Q Science
Q Science > QC Physics
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Refky Tri Saputra
Date Deposited: 27 May 2021 09:07
Last Modified: 13 Nov 2021 07:11
URI: http://repository.its.ac.id/id/eprint/60193