Wibowo, Nugraha Agung (2019) Optimasi Time Dial Setting (TDS) dan Tipe Kurva Relay Arus Lebih Menggunakan Adaptive Modified Firefly Algorithm Pada Sistem Kelistrikan PT. Pupuk Kujang Cikampek Dengan Mempertimbangkan Karakteristik Beban dan Manuver Operasi. Masters thesis, Institut Teknologi Sepuluh November.
Preview |
Text
07111750010005-Master_Thesis.pdf - Accepted Version Download (4MB) | Preview |
Abstract
Dalam sistem kelistrikan dunia industri sering dijumpai relay arus lebih sebagai salah satu peralatan dalam sistem proteksi listrik. Untuk mendapatkan sistem proteksi yang handal dan selektif, maka diperlukan penentuan dan pengaturan nilai parameter yang tepat pada relay arus lebih. Pengaturan beberepa parameter tersebut adalah arus pick up (I¬p), Time Dial Setting (TDS), dan tipe kurva,untuk mendapatkan waktu kerja relay (top) yang sesuai. Sehingga Penentuan nilai TDS dan pemilihan tipe kurva menjadi salah satu permasalahan yang sering ditemukan dikarenakan dalam proses perhitungannya membutuhkan waktu yang sangat lama yang diakibatkan karena. Sehingga metode optimasi dengan menggunakan kecerdasan buatan sangat diperlukan untuk dapat mempercepat proses perhitungan dalam menentukan nilai dari TDS dan tipe kurva yang akan digunakan. Dalam penentuan nilai TDS dan tipe kurva perlu mempertimbangkan batasan – batasan praktis yang sudah ada seperti decrement curve pada generator, damaged curve peralatan dan motor starting curve agar sistem koordinasi yang dihasilkan dapat bekerja secara selective dan dapat melindungi peralatan-peralatan listrik dalam sistem kelistrikan yang ada tanpa menggangu proses produksi. Penelitian yang digunakan berdasarkan kasus nyata pada dunia industry yaitu PT. Pupuk Kujang Cikampek. Hasil penelitian yang dilakukan menunjukan bahwa metode yang digunakan mampu menghasilkan TDS dan tipe kurva yang sesuai dengan batasan – batasan praktis yang digunakan dan dengan menggunakan AMFA dapat menghasilkan titik konvergensi dengan nilai best cost yang lebih baik.
===============================================================================================
In the industrial world electricity system is often found overcurrent relays as one of the equipment in an electrical protection system. To obtain a reliable and selective protection system, it is necessary to determine and adjust the appropriate parameter values for overcurrent relays. The settings for a number of these parameters are the pickup current, Time Dial Setting (TDS), and curve type, to get the appropriate relay (top) work time. So that the determination of TDS values and selection of curve types is one of the problems that are often found because in the calculation process requires a very long time due to. So that the optimization method using artificial intelligence is very necessary to be able to speed up the calculation process in determining the value of the TDS and the type of curve to be used. In determining the TDS value and curve type it is necessary to consider existing practical limits such as decrement curves on the generator, damaged curve equipment and motor starting curves so that the resulting coordination system can work selectively and can protect electrical equipment in the existing electrical system without disturbing the production process. The research used is based on a real case in the world of industry, namely PT. Pupuk Kujang Cikampek. The results of the research conducted show that the method used is able to produce TDS and type of curves that are in accordance with the practical limits used and by using AMFA can produce a convergence point with a better value for best cost.
Item Type: | Thesis (Masters) |
---|---|
Additional Information: | RTE 621.319 2 Wib o-1 2019 |
Uncontrolled Keywords: | firefly Algorithm ,overcurrent relay, coordination protection, motor starting curve |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays. Protective relays--Security measures. |
Divisions: | Faculty of Industrial Technology > Electrical Engineering > 20101-(S2) Master Thesis |
Depositing User: | Nugraha Agung Wibowoq |