Rekonfigurasi Jaringan Distribusi pada PT. PLN (Persero) ULP Menganti Menggunakan Selective Particle Swarm Optimization untuk Meningkatkan Efisiensi Jaringan Distribusi

Kirana, Putu Diah Nitya (2019) Rekonfigurasi Jaringan Distribusi pada PT. PLN (Persero) ULP Menganti Menggunakan Selective Particle Swarm Optimization untuk Meningkatkan Efisiensi Jaringan Distribusi. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111540000143-Undergraduate_Theses.pdf]
Preview
Text
07111540000143-Undergraduate_Theses.pdf

Download (8MB) | Preview

Abstract

Semakin padatnya pemukiman dan perindustrian, maka permintaan energi listrik juga semakin meningkat. Sistem distribusi merupakan sistem yang menyalurkan energi listrik dari sistem transmisi menuju ke konsumen. Dengan adanya penambahan beban, maka mengakibatkan perluasan atau penambahan jaringan listrik. Hal tersebut dapat menimbulkan permasalahan pada jaringan seperti losses, jatuh tegangan dan juga gangguan listrik lainnya. Losses dan jatuh tegangan ini dipengaruhi oleh parameter utama yaitu arus resistansi dan reaktansi penyulang. Oleh karena itu, untuk memperoleh jaringan yang optimal maka perlu dilakukan perubahan konfigurasi yang bertujuan untuk mengurangi rugi-rugi daya sistem dan membebaskan beban terlalu berat dalam jaringan (over load). Pada tugas akhir ini metode Selective Particle Swarm Optimization (SPSO) diaplikasikan pada sistem distribusi 63 bus dengan tiga penyulang di PT. PLN (Persero) ULP Menganti. Ketiga penyulang tersebut yaitu Penyulang Domas, Penyulang An Nur dan Penyulang Cahaya Baru. Metode ini bertujuan untuk menemukan optimasi dari kombinasi switch yang dapat meminimalisasi besar losses pada jaringan. Hasil simulasi menunjukkan penurunan rugi-rugi daya nyata dari 790,0614 kW menjadi 745,3004 kW atau sebesar 5,6655% saat rata-rata waktu beban puncak dan perbaikan kualitas tegangan dengan tegangan minimal pada sistem dari 0,89036 p.u menjadi 0,90373 p.u. ==============================================================================================================================
The more dense settlements and industries, the demand for electrical energy also increases. Distribution system is a system which delivers the electricity from transmission system to the consumers. With the addition of the load, it results in the expansion or addition of the electrical network. This can cause many network problems such as losses, voltage drop and other electrical disturbances. Losses and voltage drop are affected with two main parameters, there are network resistance and reactance. Therefore, to obtain a better optimal network, it is necessary to make change through reconfiguration. This reconfiguration is a potential solution to minimize power losses and overload network. In this final project, the Selective Particle Swarm Optimization (SPSO) method is applied to the 63 bus distribution system for three feeders at PT. PLN (Persero) ULP Menganti, which are Domas Feeder, An Nur Feeder, and Cahaya Baru Feeder. This method is proposed to find the optimal combination of switches that will minimize the power losses of the network. The simulation results show the minimization of power losses from 790,0614 kW to 745,3004 kW or by 5,6655% when the average peak load time and improve the minimum quality of the system from 0,89036 p.u to 0,90373 p.u.

Item Type: Thesis (Other)
Additional Information: RSE 621.319 Kir r-1 2019
Uncontrolled Keywords: Jaringan Radial, Rugi Daya, SPSO, Rekonfigurasi
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK3030 Electric power distribution systems
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Kirana Putu Diah Nitya
Date Deposited: 12 Jan 2023 03:39
Last Modified: 12 Jan 2023 03:39
URI: http://repository.its.ac.id/id/eprint/63513