Arus inrush merupakan suatu fenomena transien yang umum terjadi pada peralatan listrik yang menggunakan prinsip kerja elektromagnetik. Arus inrush dapat menimbulkan beberapa masalah, seperti: menyebabkan kesalahan operasi dari rele proteksi, mengurangi umur dari transformator, dan biasanya dapat mengurangi kualitas daya dari suatu sistem tenaga listrik. Pada studi ini akan dibahas pengaruh dari sudut penyalaan saat proses energize terhadap arus inrush yang timbul pada transformator 3 fasa. Studi dilakukan dengan melakukan pengujian terhadap transformator uji 3 fasa 3 kVA dengan pembuatan modul pengujian untuk mengatur sudut penyalaan dengan 7 variasi sudut penyalaan dimulai dari 0° hingga 180°. Hasil dari pengujian ini adalah didapat bahwa arus inrush yang timbul akan bernilai maksimum ketika tegangan yang diinjeksi ke transformator berada di titik minimum atau berada pada sudut penyalaan 0° atau 180°, sedangkan arus inrush akan bernilai minimum ketika tegangan yang diinjeksi ke transformator berada di titik maksimum atau berada pada sudut penyalaan 90°. Hal tersebut dikarenakan kebutuhan fluks dalam transformator mencapai besaran tertentu untuk mencapai titik saturasi yang diinginkan.
===============================================================================================================================
Inrush current is a transient phenomenon that commonly happen in electrical equipment that used electromagnetic principle. Inrush current caused some problem, for example: protection relay operation fault, decrease the lifetime of transformer, and usually decrease power quality in power system. In this study, will be discussed about the effect of energizing switching angle on inrush current which arises in 3-phase transformer. Studies conducted with an experiment in 3 kVA 3-phase transformer and a module to control the switching angle with 7 variations of switching angle from 0° to 180°. The result of the experiments is the inrush current will be at maximum value when the voltage that applied is at minimum value or at switching angle 0° and 180°, meanwhile the inrush current will be at minimum value when the voltage that applied is at maximum value or at switching angle 90°. This is because flux in the transformer need to reach some value to get the saturation desired.

Item Type: Thesis (Other)
Additional Information: RSE 621.314 Jov a-1 2019
Uncontrolled Keywords: Arus Inrush, Sudut Penyalaan, Transformator 3 Fasa, Pengujian
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2551 Electric transformers.
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK6565.T7 Transformers
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Muhammad Renaldy Jovananda
Date Deposited: 06 Mar 2023 01:15
Last Modified: 06 Mar 2023 01:15
URI: http://repository.its.ac.id/id/eprint/63581

Actions (login required)

View Item View Item