Perhitungan CCT (Critical Cleating Time) berdasarkan critical trajectory menggunakan hilangnya sinkronisasi pada sistem multi mesin dengan mempertimbangkan kondisi unbalance

Sari, Ruliana Puspita (2015) Perhitungan CCT (Critical Cleating Time) berdasarkan critical trajectory menggunakan hilangnya sinkronisasi pada sistem multi mesin dengan mempertimbangkan kondisi unbalance. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2211100012_Undergraduate_Thesis.pdf]
Preview
Text
2211100012_Undergraduate_Thesis.pdf

Download (4MB) | Preview

Abstract

Perhitungan critical clearing time (CCT) merupakan hal yang
penting karena berhubungan dengan kestabilan sistem akibat gangguan
besar seperti hubung singkat. Bekerjanya pemutus daya untuk
mengisolasi gangguan tidak menjamin sistem akan kembali stabil. Sistem
akan kembali stabil apabila gangguan dihilangkan sebelum waktu
pemutus kritisnya dan sistem tidak stabil bila gangguan dihilangkan
setelah waktu pemutus kritisnya. Perhitungan CCT dengan numerical
simulation memberikan hasil yang akurat, namun memerlukan proses
iterasi yang lama dan nilai CCT yang diperoleh masih berada dalam range
stabil dan tidak stabil. Oleh karena itu, diusulkan metode baru untuk
memperoleh nilai CCT yakni dengan pendekatan critical trajectory.
Metode ini sangat efektif karena tidak memerlukan waktu lama (direct
method). Hampir semua gangguan hubung singkat yang terjadi pada
sistem tenaga adalah gangguan asimetri. Gangguan asimetri
menyebabkan arus berlebih pada fasa yang terkena gangguan sehingga
menyebabkan kondisi unbalance. Pada tugas akhir ini perhitungan CCT
dilakukan dengan metode hilangnya sinkronisasi akibat gangguan
asimetri. Hasil simulasi yang dilakukan menunjukkan bahwa nilai CCT
untuk tiap gangguan yang terjadi memiliki nilai hampir sama. Pada sistem
3 generator 9 bus Fouad dan Anderson tanpa damping nilai CCT yang
diperoleh pada semua jenis gangguan sekitar 0,21-0,22 detik, sedangkan
pada sistem 7 generator 57 bus IEEE tanpa damping nilai CCT yang
diperoleh pada semua jenis gangguan sekitar 0,10-0,11 detik.

============================================================================================

Calculation of critical clearing time (CCT) is important because it relates
to the stability of system as a result of major disturbances such as short
circuit. Breaker operation to remove disturbance does not guarantee the
system stability. If disturbance is eliminated before critical clearing time,
the system will return to stable state. Conversely, if the disturbance is
eliminated after critical time, the system becomes unstable. CCT obtained
by numerical simulation calculations provide accurate results, but require
a long process of iteration and CCT obtained are still in the range of stable
and unstable. Therefore, new method proposed to obtain CCT by
approach of critical trajectory. This method is very effective because it
does not require a long time (direct method). Almost all short circuit
occurred in power system is asymmetry fault. Asymmetry fault causes
excessive current in phase fault that causes an unbalanced condition. In
this final project calculation of CCT use loss of synchronism method by
considering the condition of unbalance caused by asymmetry fault. The
simulation results show CCT for each fault occurred approximately has
same value. CCT obtained in 3 generators 9 buses Fouad and Anderson
system without damping on each fault type is about 0,21-0,22 second,
while in 7 generators and 57 buses system without damping on each fault
type is about 0,10-0,11 second.

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.312 Sar p
Uncontrolled Keywords: Analisis kestabilan transien; critical clearing time (cct); critical trajectory; hilangnya sinkronisasi; unbalance fault
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK4035.R4 Refrigeration and refrigerating machinery
Divisions: Faculty of Industrial Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: - Taufiq Rahmanu
Date Deposited: 09 Oct 2019 04:25
Last Modified: 09 Oct 2019 04:25
URI: http://repository.its.ac.id/id/eprint/71075

Actions (login required)