Kondensor merupakan salah satu jenis heat exchanger
yang berfungsi mengkondensasikan fluida gas menjadi cair.
Dibutuhkan material tube yang kuat dan dapat melakukan
perpindahan panas yang baik agar tidak terjadi penurunan laju
perpindahan panas di dalam kondensor. Jika laju perpindahan
panas rendah, mengakibatkan kerja netto akan semakin
meningkat. Mengetahui peran kondensor sangat penting dalam
suatu siklus, maka perlu dilakukan analisa laju perpindahan panas
kondensor Unit 3 PT. PLTU UP Gresik. Kondensor Unit 3 adalah
kondensor yang telah di redtubing dengan material tube titanium.
Titanium memiliki kekuatan material yang lebih kuat
dibandingkan aluminium brass material sebelumnya, sehingga
kebocoran pada tube dapat dikurangi dengan menggunakan
material titanium.
Data yang diambil dari tugas akhir ini adalah data ratarata
aktual selama 1 bulan, yaitu bulan Juni. Metode perhitungan
untuk menghitung laju perpindahan panas dan efektivitas adalah
Log Mean Temperature Different (LMTD) dan Effectiveness –
Number of Transfer Unit (NTU).
Dari hasil perhitungan, dengan data kevakuman yaitu
0,079288 bar pada bulan Juni diketahui bahwa laju perpindahan
panas sebesar 194,1226889 MW dengan efektivitas sebesar
0,9978764. Laju perpindahan panas pada kondensor dipengaruhi
oleh kondisi kevakuman kondensor. Semakin tinggi kevakuman
kondensor maka steam semakin mudah menuju kondensor,
sehingga meningkatkan performa dari kondensor.
===============================================================================================
Condensor is component that has an important rate in the
efficiency of the cycle, it uses for for condensate from gas to
liquid. Needed tube material strong and can heat transfer good for
not effect heat transfer decreases on condenser. If the heat transfer
small, netto worl’ will increase. To know how condenser work if
need to calculate the heat tranfer of condensor at PT. PJB UP.
Gresik PLTU Unit 3. Condensor unit 3 has been redtubing with
materials titanium tube. Titanium have strength than aluminium
brass, so lekeage on the tube can decreaes wich material titanium.
In this final project, data taken the average of actual
condition condenser for June. Whereas, the method used in this
calculation of the heat transfer-rate and effectiveness is Log
Mean Temperature Difference (LMTD) and Number of Transfer
Unit (NTU) Method.
From the calculation, it known that the vacuum data on
June 2014 is 0,079288 bar and it known that the heat transfer is
194,1226889 MW witch effectiveness is 0,9978764. Heat transfer
on condensor be affected to vacuum condition. The higher
vacuum steam condensers then the easier it towards the
condenser, thereby increasing the performance of the condenser .

Item Type: Thesis (Diploma)
Additional Information: RSM 621.402 2 Suc a
Uncontrolled Keywords: Kondensor, Laju Perpindahan Panas, Efektivistas
Subjects: Q Science > QC Physics > QC320 Heat transfer
Divisions: Faculty of Industrial Technology > Mechanical Engineering > 21401-(D3) Diploma 3
Depositing User: Mr. Marsudiyana -
Date Deposited: 13 Dec 2019 08:40
Last Modified: 13 Dec 2019 08:40
URI: http://repository.its.ac.id/id/eprint/72369

Actions (login required)

View Item View Item