Rumah kabel bawah tanah adalah suatu ruangan dimana
didalamnya terdapat beberapa kabel listrik tegangan menengah pada
instalasi gardu induk PLN. Pada beberapa gardu induk di Surabaya
terdapat beberapa kabel yang isolasinya sudah rusak. Kerusakan pada
isolasi kabel ini biasanya dikarenakan oleh rendaman air pada kabel
dengan waktu yang lama. Rendaman air ini berasal dari air hujan
maupun air limbah pada selokan disekitar gardu induk yang datarannya
lebih tinggi sehingga menimbulkan rembesan air ke gardu induk
khususnya pada rumah kabel. Dengan adanya hal ini, petugas dituntut
untuk selalu tanggap dalam mengawasi keadaan rumah kabel terhadap
rembesan air yang bisa membanjiri tempat tersebut dan memberi
informasi kapan waktunya air harus dibuang. Cara pelaporan ini
terbilang kurang efektif dan efisien.
Alat ini mampu mengukur ketinggian air secara real time, dan
mampu mengontrol ketinggian air. Jika tinggi air lebih dari 13 cm maka
pompa 2 akan on, dan pompa 2 akan off apabila ketinggian air yang
semula lebih dari 13 cm menjadi kurang dari 3 cm. Kemudian pada
pompa 1 on apabila air menggerakkan sensor pada tandon dengan
ditandai status sensor tandon on. Pembacaan ketinggian air dan status
pompa air akan ditampilkan pada LCD dan PC melalui software
LabVIEW dan disimpan pada database Ms.Excel PC.
Dari hasil Tugas Akhir ini dapat memonitor ketinggian air dan
kerja pompa air on off secara real time melalui PC maupun pada LCD
panel monitoring. Pada PC data tersimpan secara otomatis selang 1
menit ketika ketinggian air dibawah 10 cm dan ketika diatas 10 cm
(kritis) data tersimpan selang 30 detik kemudian dari hasil itu di
download pada LabVIEW untuk dijadikan database.
===================================================================================================
Underground cable house is a room in which there are several
medium voltage power cables the installation of substations PLN. In
some substations in Surabaya, there are several cable insulation is
damaged. Damage to the cable insulation is usually caused by a water
immersion at a cable with a long time. This water immersion comes
from rain water and waste water in sewers around substations that
higher plains causing water seepage into the substation, especially in
cable house. With the existence of this, officers are required to be
responsive to monitor the state of the cable house to water seepage that
could overwhelm the place it and provide information when to water
should be discThe way of reporting is somewhat less effective and
efficient .
The prototype is capable to measure the water level in real time,
and it is able to control the water level. If the condition of water level is
upper 13 cm, then pump 2 will be on, and pump 2 will be off if the water
level were originally more than 13 cm became less than 3 cm. Then the
pump 1 on when the water moves sensor on the tank with tank sensor
status marked on. The reading of the water level and the water pump
status is displayed on the LCD and PC through LabVIEW software and
will be saved on a database Ms.Excel PC
From the results of this final project can monitor the water level
and water pump working on off in real time via the PC or on the LCD
panel monitoring. Data will be saved on the PC automatically lapse 1
minute when the water level below 10 cm and when over 10 cm (critical)
data will be saved interval of 30 seconds later from the results
downloaded in LabVIEW to be used as database.
Item Type: | Thesis (Diploma) |
---|---|
Additional Information: | RSE 629.895 Mau m |
Uncontrolled Keywords: | Monitoring, Kontrol Pompa Air, Sensor Ketinggian Air |
Subjects: | T Technology > TJ Mechanical engineering and machinery > TJ799 Diesel motor--Electronic control. |
Divisions: | Faculty of Industrial Technology > Electrical Engineering > 20401-(D3) Diploma 3 |
Depositing User: | Mr. Marsudiyana - |
Date Deposited: | 17 Dec 2019 07:38 |
Last Modified: | 17 Dec 2019 07:38 |
URI: | http://repository.its.ac.id/id/eprint/72401 |
Actions (login required)
View Item |