Eliminasi Fluks Sisa Pada Transformator Satu Fasa Menggunakan Metode Penggeseran Kutub Pada Sumber Tegangan DC - Elimination Of Residual Flux In Single Phase Transformer By The Application Of An Alternating Polarity DC Voltage Source

Nurdianto, Ryan (2016) Eliminasi Fluks Sisa Pada Transformator Satu Fasa Menggunakan Metode Penggeseran Kutub Pada Sumber Tegangan DC - Elimination Of Residual Flux In Single Phase Transformer By The Application Of An Alternating Polarity DC Voltage Source. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2212100003-Undergraduate Thesis.pdf]
Preview
Text
2212100003-Undergraduate Thesis.pdf - Published Version

Download (2MB) | Preview

Abstract

Transformator merupakan bagian yang penting dalam sistem
kelistrikan. Pada saat energisasi transformator, terjadi salah satu kejadian
yang tidak bisa dilepaskan yaitu fenomena arus inrush. Arus inrush yang
tinggi dapat menyebabkan penurunan kualitas transformator,
menimbulkan kegagalan koordinasi sistem proteksi transformator dan
menurunkan kekuatan isolasi belitan pada transformator. Arus inrush
yang tinggi salah satu penyebabnya adalah adanya fluks sisa dari
transformator. Arus inrush pada proses energisasi dapat mencapai nilai
10-20 kali arus rating. Pada studi ini akan menguji dan membuat sebuah
alat untuk mengurangi besar arus inrush dengan cara mengurangi besar
nilai fluks sisa dari transformator. Alat ini bekerja dengan cara menggeser
(switching) polaritas sumber tegangan DC. Besarnya tegangan dijadikan
variabel dengan frekuensi yang tetap (Variable Voltage-Constant
Frequency/VVCF). Hasil yang diperoleh dari studi ini adalah besar nilai
arus inrush transformator sesudah didemagnetisasi mengalamami
penurunan besar nilai arus. Pada dua kali pengambilan data pada sudut
penyalaan 00 penurunan nilai arus inrush terjadi pada nilai 31.68A ke
nilai 25.55A dan terjadi pada nilai 30.12A ke nilai 25.25A, sedangkan
pada sudut penyalaan 900 penurunan nilai arus terjadi pada nilai 9.22A
ke nilai 5.75A dan terjadi pada nilai 8.22A ke nilai 5.50A.
========================================================================================================================
The transformer is an important part of the electrical system. At the
time of transformer energizer, the occurrence of any event that can’t be
released, namely the inrush currents phenomenon. High inrush currents
caused loss of quality transformer, failure of protection systems
coordination and lower isolation power of transformer windings on the
transformer. The residual fluxs of the transformer caused high inrush
currents. Inrush currents on the energizer can reach a value of 10-20
times the current rating. In this study will examine and make a major tool
to reduce the inrush current by reducing the large value of residual fluxs
of transformer. This tool works by switching polarity of the DC voltage
source. The amount of voltage is used as a variable to a fixed frequency (
Variable Voltage-Constant Frequency / VVCF). The results obtained
from this study is decreasing value of inrush current after
demagnetitation. At twice the data retrieval on the firing angle 00,
decreasing of inrush currents occured in the value of 31.68A to 25.55A
and in the value of 30.12A to 25.25A, while at the firing angle of
900,decreasing of inrush currents occured in the value 9.22A to 5.75A and
in the value of 8.22A to 5.50A value.

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.314 Nur e
Uncontrolled Keywords: transformator, arus inrush, Variable Voltage-Constant Frequency/VVCF, transformer, inrush currents, Variable Voltage-Constant Frequency/VVCF
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission
Divisions: Faculty of Industrial Technology > Electrical Engineering
Depositing User: ansi aflacha
Date Deposited: 18 Dec 2019 04:11
Last Modified: 18 Dec 2019 04:11
URI: http://repository.its.ac.id/id/eprint/72425