Evaluasi Rele Arus Lebih Menggunakan Kurva Batas Kestabilan Transien Pada Sistem Kelistrikan PT. Pupuk Sriwidjaja Palembang

Husin, Ramdhan (2021) Evaluasi Rele Arus Lebih Menggunakan Kurva Batas Kestabilan Transien Pada Sistem Kelistrikan PT. Pupuk Sriwidjaja Palembang. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111740000056_Undergraduate_Thesis.pdf] Text
07111740000056_Undergraduate_Thesis.pdf - Accepted Version
Restricted to Repository staff only until 1 October 2023.

Download (2MB) | Request a copy

Abstract

Gangguan hubung singkat kerap terjadi pada sistem tenaga listrik. Gangguan hubung singkat dapat menyebabkan generator pada sistem kehilangan sinkronisasinya walaupun rele arus lebih sudah bekerja. Untuk mencegah kehilangan sinkronisasi pada generator, dibentuk kurva batas kestabilan transien. Kurva batas kestabilan transien adalah suatu kurva yang membatasi daerah kerja rele arus lebih agar ketika rele tersebut bekerja, generator-generator pada sistem tidak kehilangan sinkronisasinya. Untuk membentuk kurva batas kestabilan transien, perlu dilakukan analisis kestabilan transien dan hubung singkat pada sistem. Dari analisis yang telah dilakukan akan terbentuk titik-titik kestabilan yang kemudian digunakan untuk membentuk kurva batas kestabilan transien. Setelah kurva batas kestabilan transien terbentuk, rele arus lebih pada pabrik 4 PT. Pupuk Sriwidjaja Palembang di evaluasi kestabilannya. Berdasarkan kurva batas kestabilan transien, setting eksisting rele arus lebih pabrik 4 dinyatakan stabil. Oleh karena itu, tidak perlu dilakukan resetting pada rele-rele tersebut.
================================================================================================
Short circuit faults often occur in electric power systems. Short circuit faults can cause the generator in the system to lose synchronization even though the overcurrent relay is working. To prevent loss of synchronization in the generator, a transient stability limit curve is formed. The transient stability limit curve is a curve that limits the working area of the overcurrent relay. So that when the relay operates, the generators in the system do not lose their synchronization. To form a transient stability limit curve, it is necessary to perform transient stability and short circuit analysis on the system. From the analysis that has been carried out, stability points will be formed which are then used to form a transient stability limit curve. After the transient stability limit curve is formed, the overcurrent relay at factory 4 PT. Pupuk Sriwidjaja Palembang is evaluated for its stability. Based on the transient stability limit curve, the existing setting of factory 4 overcurrent relay is stable. Therefore, there is no need to resetting the relays.

Item Type: Thesis (Undergraduate)
Uncontrolled Keywords: Overcurrent relay, short circuit, transient stability, transient stability limit curve, rele arus lebih, Hubung singkat, kestabilan transien, kurva batas kestabilan transien.
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1010 Electric power system stability. Electric filters, Passive.
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK3226 Transients (Electricity). Electric power systems. Harmonics (Electric waves).
Divisions: Faculty of Intelligent Electrical and Informatics Technology (ELECTICS) > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Ramdhan Husin
Date Deposited: 15 Aug 2021 18:55
Last Modified: 15 Aug 2021 18:55
URI: http://repository.its.ac.id/id/eprint/86776