Raharja, Budi (2021) Sistem Proteksi dan Peringatan Motor Induksi 3 Fasa Terhadap Gangguan Unbalance Menggunakan Metode Fuzzy Logic dengan Tampilan Aplikasi Android. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.
Text
10311710000006-Undergraduate_Thesis.pdf - Accepted Version Restricted to Repository staff only until 1 October 2023. Download (4MB) | Request a copy |
Abstract
Motor induksi tiga fasa merupakan salah satu mesin listrik yang banyak digunakan di dunia industri. Motor induksi tiga fasa dinilai sangat penting dalam dunia industri, sehingga motor induksi diharuskan bekerja dengan baik dan aman. Salah satu permasalahan pada sistem tenaga listrik adalah gangguan unbalance. Unbalance terjadi akibat gangguan, perubahan beban, dan perubahan kondisi pada sistem. Hal ini tentunya akan memberikan pengaruh motor induksi 3 fasa tidak bekerja dengan optimal dan tidak pada kondisi normal motor.
Dari permasalahan tersebut, maka dibuat suatu sistem yang mampu melakukan proteksi dan peringatan motor induksi 3 fasa terhadap gangguan ketidakseimbangan arus dan tegangan berdasarkan standar ANSI sebesar ±3% menggunakan metode Fuzzy Logic dan tanpilan aplikasi android.
Berdasarkan hasil pengujian yang dilakukan pada motor induksi 3 fasa, sistem proteksi dan peringatan menggunakan metode Fuzzy logic dapat bekerja dengan baik. Namun terdapat error sebesar dari perbandingan output hasil simulasi matlab dan realisasi sistem sebesar 1,21%. Untuk sistem monitoring dan peringatan pada aplikasi masih terdapat delay sebear 2-4 detik dan untuk cara kerja keseluruhan sistem telah sesuai dengan fungsi yang ditetapkan.
================================================================================================
The three-phase induction motor is one of the most widely used electrical machines in the industrial world. Three-phase induction motors are considered very important in the industrial world, so induction motors are required to work properly and safely. One of the problems in the electric power system is unbalance disturbance. Unbalance occurs due to disturbances, changes in load, and changes in system conditions. This of course will have the effect of a 3-phase induction motor not working optimally and not under normal motor conditions.
From these problems, a system is made that is able to protect and warn 3-phase induction motors against current and voltage imbalance disturbances based on the ANSI standard of ±3% using the Fuzzy Logic method and the android application display.
Based on the results of tests carried out on a 3-phase induction motor, the protection and warning system using the Fuzzy logic method can work well. However, there is an error of 1.21% from the comparison of the output of the MATLAB simulation results and the realization of the system. For monitoring and warning systems in the application there is still a delay of 2-4 seconds and for the way the whole system works, it is in accordance with the specified function.
Item Type: | Thesis (Undergraduate) |
---|---|
Uncontrolled Keywords: | Motor Induksi 3 Fasa, Sistem Proteksi, Monitoring, Fuzzy Logic, 3 Phase Induction Motor, Protection System, Monitoring, Fuzzy Logic |
Subjects: | Q Science > QA Mathematics > QA9.64 Fuzzy logic T Technology > TJ Mechanical engineering and machinery > TJ223 PID controllers T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2785 Electric motors, Induction. T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK3070 Automatic control T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK4055 Electric motor T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK7872 Electric current converters, Electric inverters. |
Divisions: | Faculty of Vocational > 36304-Automation Electronic Engineering |
Depositing User: | Budi Raharja |
Date Deposited: | 25 Aug 2021 04:36 |
Last Modified: | 25 Aug 2021 04:36 |
URI: | http://repository.its.ac.id/id/eprint/89514 |
Actions (login required)