Gedung utama bangunan khusus RSUD Dr. Moh. Soewandhie Kota Surabaya yang merupakan bangunan beton bertulang dengan 8 Lantai dan 1 Basement ditinjau sebagai bangunan eksisting pada penulisan proyek akhir ini. Bangunan ini memiliki perencanaan awal menggunakan SRPMK sesuai SNI 1726-2012, 1727-2013 dan SNI 2847-2019. Bangunan ini dibangun di atas tanah dengan kondisi tanah lunak (kelas situs SE) dan berdasarkan fungsinya, yaitu rumah sakit, termasuk kedalam kategori resiko IV. Studi ini melakukan evaluasi dan perkuatan bangunan eksisting menggunakan fluid viscous damper (FVD) sebagai alat penahan gempa karena kapasitas elemen eksisting dan simpangan tidak memenuhi syarat ijin setelah dianalisa dengan peraturan gempa terbaru SNI 1726 - 2019.
Pengerjaan proyek akhir ini diawali dengan menganalisis struktur eksisting menggunakan peraturan gempa SNI 1726 – 2012. Kemudian menganalisis struktur eksisting menggunakan peraturan gempa terbaru SNI 1726 – 2019. Terakhir, Perkuatan bangunan eksisting dengan menambahkan FVD sebagai alat penahan gempa pada struktur. Studi ini melakukan uji coba dengan 12 konfigurasi penempatan FVD.
Hasil analisa bangunan eksisting dengan SNI 1726 – 2012 didapatkan nilai simpangan sebesar 53,28 mm di arah X dan 51,78 di arah Y. Setelah di analisa dengan SNI 1726-2019 didapatkan hasil evaluasi simpangan sebesar 82,45 mm di arah X dan 79,85 mm di arah Y, dimana pada lantai 2 - 7 tidak memenuhi syarat simpangan ijin dan menunjukkan kapasitas elemen eksisting melebihi kapasitas ijin. Percobaan perkuatan dengan 12 konfigurasi FVD dilakukan dengan variasi jumlah dan penempatan FVD. Berdasarkan pertimbangan gaya geser dasar dan nilai simpangan dipilih konfigurasi 11 dengan menggunakan32 buah FVD berkapasitas 2000 kN (FVD model 17170). Semua FVD dipasang diluar rangka dengan masing - masing 16 FVD pada arah X dan Y. FVD dipasang dengan breising HSS Circle dengan diameter 318,5 mm dan tebal 9 mm, dengan sistem sambungan gusset plate dan pin baja. Kapasitas elemen eksisting setelah dipasang FVD berada dalam batas kekuatan yang dijinkan.
================================================================================================================================
The special main building Dr. Moh. Soewandhie in Surabaya is being reviewed as existing building in this study. This building has preliminary design using reinforcement concrete with SMRFs according to SNI 1726 – 2012, 1727 – 2013, and 2847 – 2019. This building is built on land with soft soil conditions (SE site class) and based on its function is included in risk category IV. This study evaluated and strengthening the structure with fluid viscous damper (FVD) due to analysis result capacity of existing element and displacement didn’t fulfill the required limit according to latest earthquake regulation SNI 1726 – 2019.
This final project begins with analyzed of the existing structure with earthquake load based on SNI 1726 – 2012. Then, analyzed the existing structure with newest earthquake load based on SNI 1726 – 2019. Last, analyzed the structure after strengthened with FVD. This study conducted a trial with 12 FVD placement configurations.
The results of existing building analysis according SNI 1726-2012 showed that displacements at direction X and Y are 53.28 mm and 51.78 mm. After existing building being evaluated according SNI 1726-2019, The displacements showed at direction X and Y are 82.45 mm and 79.85 mm, where at story 2 until 7 didn’t fulfill the required limits and the capacity of existing element exceed the allowable strength. So that, the existing building being retrofitted with 32 units FVD which capacity of damper is 2000 kN each. All FVD installed at the exterior of the building with total 16 FVDs in each direction X and Y. FVDs are installed with bracing HSS Circle with a 318,5 mm diameter and 9 mm thickness with gusset plate and pin connection, the results of the examination after retrofitting, the displacement in the X direction was reduced by 50.75% to 40,61 mm and the Y direction was reduced by 49,41% to 40,41 mm. The capacity of the existing element after using FVDs is within the limits of allowable strength.

Item Type: Thesis (Other)
Uncontrolled Keywords: SRPMK, perkuatan, fluid viscous damper, simpangan, breising
Subjects: T Technology > TA Engineering (General). Civil engineering (General)
Divisions: Faculty of Vocational > Civil Infrastructure Engineering (D4)