Medwin, Daniel Ryan (2023) Rancang Bangun Alat Pembangkit Busur Api Listrik Paralel Sistem Tegangan Rendah yang Terintegrasi. Other thesis, Institut Teknologi Sepuluh Nopember.
Text
07111940000139-Undergraduate_Thesis.pdf - Accepted Version Restricted to Repository staff only until 1 September 2025. Download (5MB) | Request a copy |
Abstract
Arc Flash menjadi salah satu penyebab utama terjadinya kebakaran oleh listrik, terutama pada sistem instalasi listrik perumahan. Arc Flash dapat terjadi akibat adanya hubung singkat, yang terjadi karena kontak langsung kedua konduktor yang berbeda potensial memiliki isolasi yang tidak standar, sehingga bagian konduktif kabel saling bersentuhan. Studi mengenai fenomena busur api ini terutama pada alat pembangkit busur api sudah cukup banyak, namun dalam studi mengenai arc flash paralel yang terdahulu, alat arc generator masih belum terintegrasi dengan kamera termal dan akustik, sehingga dalam studi ini dibangun sebuah mekanisme pembangkit busur api paralel pada tegangan rendah yang sudah terintegrasi dengan kamera termal yang ada. Studi ini menggunakan kamera akustik Fluke ii900, kamera termal FLIR Ex-Series, dan NI 9775 serta NI 9246 sebagai alat akuisisi data arus dan tegangan. Studi ini juga dapat mensimulasikan dan menghasilkan data karakteristik fenomena busur api dari kontak paralel. Studi ini dilakukan dengan batasan sistem tegangan rendah 220 V dan penggunaan kabel serabut 2,5 mm2 dengan beban resistif linier dan variasi besar beban serta jumlah serabut. Karakteristik didapatkan dari dilakukannya kontak antara kabel serabut fasa dan netral hingga terbangkitkan busur api yang kemudian datanya direkam melalui integrasi program LabVIEW. Hasil akhir dari studi ini adalah sebuah alat arc generator yang dapat mensimulasikan fenomena busur api paralel tegangan rendah pada beban yang cukup besar, yaitu sampai 4400 W dengan cukup baik dan menampilkan karakteristik seperti suhu, arus, energi, dan elemen akustik dari busur api yang terbangkitkan. Berdasarkan hasil data pengujian, didapatkan peningkatan nilai rata-rata sebesar 3% pada energi, 2% pada arus arcing maksimum, 10% pada suhu arcing, dan 1,5% pada nilai akustik seiring bertambahnya jumlah serabut.
======================================================================================================================================
Arc Flash is one of the main causes of fires caused by electricity, especially in residential electrical installation systems. Arc Flash can occur due to a short circuit, which occurs due to the direct contact of two conductors with different potentials that have non-standard insulation, so that the conductive parts of the cable touch each other. There have been quite a number of studies on the arc phenomenon, especially in arc generators, but in previous studies of parallel arc flash, the arc generator was not yet integrated with thermal and acoustic cameras, so in this study a parallel arc generator mechanism was built on low voltage integrated with existing thermal cameras. This study uses the Fluke ii900 acoustic camera, FLIR Ex-Series thermal camera, and NI 9775 and NI 9246 as current and voltage data acquisition tools. This study can also simulate and produce characteristic data of the arcing phenomenon from parallel contact. This study was carried out with a low voltage system limitation of 220 V and the use of 2.5 mm2 strand cable with a linear resistive load and variations in the magnitude of the load and the number of fibers. Characteristics are obtained from the contact between the phase and neutral fiber cables to generate an arc which is then recorded through the integration of the LabVIEW program. The end result of this study is an arc generator that can simulate the phenomenon of low voltage parallel arcing at a fairly large load, namely up to 4400 W quite well and displays characteristics such as temperature, current, energy, and acoustic elements of the generated arc. Based on the results of the test data, an increase in the average value of 3% in energy, 2% in maximum arcing current, 10% in arcing temperature, and 1.5% in acoustic value with increasing number of cable fibers.
Item Type: | Thesis (Other) |
---|---|
Uncontrolled Keywords: | Arc generator, Arcing paralel, Penginderaan akustik, Penginderaan termal, Parallel arcing, Acoustic imaging, Thermal imaging. |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK3226 Transients (Electricity). Electric power systems. Harmonics (Electric waves). T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK351 Electric measurements. |
Divisions: | Faculty of Intelligent Electrical and Informatics Technology (ELECTICS) > Electrical Engineering > 20201-(S1) Undergraduate Thesis |
Depositing User: | Daniel Ryan Medwin |
Date Deposited: | 24 Jul 2023 14:47 |
Last Modified: | 24 Jul 2023 14:47 |
URI: | http://repository.its.ac.id/id/eprint/99149 |
Actions (login required)
View Item |