Evaluasi Sistem Koordinasi Proteksi di PT Linde Gresik Menggunakan Input PLN Sebesar 150 KV Dengan Mempertimbangkan Arc Flash

Wardhana, Daffa Dhaifullah (2023) Evaluasi Sistem Koordinasi Proteksi di PT Linde Gresik Menggunakan Input PLN Sebesar 150 KV Dengan Mempertimbangkan Arc Flash. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111840000123-Undergraduate_Thesis.pdf] Text
07111840000123-Undergraduate_Thesis.pdf - Accepted Version
Restricted to Repository staff only until 1 October 2025.

Download (1MB) | Request a copy

Abstract

PT Linde adalah perusahaan yang mengkhususkan diri dalam pipa dan pasokan gas di indonesia melalui pemasangan pabrik khusus pada lokasi pelanggan. Pada perindustrian dibutuhkan sistem kelistrikan yang bekerja secara optimal dan handal guna menjaga kontinuitas daya listrik dan meminimalisir dampak yang ditimbulkan ketika terjadi gangguan. Salah satu fenomena atau gangguan yang dapat terjadi adalah fenomena arc flash atau busur api. Busur api adalah kondisi yang berbahaya akibat pelepasn energi yang disebabkan oleh bunga api listrik. Bunga api listrik timbul karena adanya arus gangguan atau disebut dengan arcing fault pada sebuah sistem kelistrikan. Saat terjadinya incident energy arc flash, yang terjadi adalah akan muncul pembakaran dari busur api. Efek dari fenomena tersebut dapat berupa ledakan dan radiasi panas. Analisa bahaya dari arc flash harus dilakukan dengan melakukan studi terhadap koordinasi proteksi dan hubungan singkat. Untuk mengukur dan mencegah terjadinya fenomena arc flash diperlukan perhitungan incident energy yang nantinya akan dibandingkan dengan data yang ada pada pengaturan di sistem proteksi industri tersebut. Hasil dari analisa yang dilakukan terhadap sistem proteksi akan dikategorikan sesuai dengan kebutuhan sistem proteksi yang ada. Untuk mengatasi gangguan fenomena arc flash, sistem proteksi perlu memiliki keandalan untuk melakukan proteksi dengan cara memutus arus gangguan yang muncul pada sistem dengan ketepatan yang baik dan waktu yang cepat. Dari hasil evaluasi koordinasi proteksi didapatkan bahwa rele sudah bekerja sesuai standar dan dapat melindungi peralatan utama seperti beban, transformator, dan sumber. Lalu untuk hasil incident energy pada setiap bus didapatkan pada kategori bahaya 2 dan 3.
======================================================================================================================================
PT Linde is a company that specializes in pipelines and gas supply in Indonesia through the installation of special plants at the customer sites. In industry, an electrical system that works optimally and reliably is needed in order to maintain the continuity of electrical power and minimize the impact caused when a disturbance occurs. One of the phenomena or disturbances that can occur is the arc flash phenomenon. Arc is a dangerous condition due to the release of energy caused by electric sparks. Electric sparks arise due to a fault current or an arcing fault in an electrical system. When an arc flash energy incident occurs, what happens is that there will be a combustion from the arc of fire. The effects of these phenomena can be in the form of explosions and heat radiation. The hazard analysis of arc flash should be carried out by conducting a study of the protection coordination and short circuit. To measure and prevent the occurrence of arc flash phenomena, it is necessary to calculate incident energy which will later be compared with existing data in the settings in the industrial protection system. The results of the analysis carried out on the protection system will be categorized according to the needs of the existing protection system. To overcome the disturbance of the arc flash phenomenon, the protection system needs to have the reliability to perform protection by breaking the fault current that appears in the system with good accuracy and fast time. From the results of the evaluation of protection coordination, it was found that the relay was working according to standards and could protect the main equipment such as loads, transformers and sources. Then the incident energy results for each bus are obtained in hazard categories 2 and 3.

Item Type: Thesis (Other)
Uncontrolled Keywords: Arc Flash, Sistem Koordinasi Proteksi, Incident Energy. Arc Flash, Protection Coordination System, Incident Energy.
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays
Divisions: Faculty of Intelligent Electrical and Informatics Technology (ELECTICS) > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Daffa Dhaifullah Wardhana
Date Deposited: 28 Jul 2023 06:35
Last Modified: 28 Jul 2023 06:35
URI: http://repository.its.ac.id/id/eprint/99963