Pengurangan Insiden Energi Arc Flash Dengan Menggunakan Metode Zone Selective Interlocking Pada PT. Conocophilips Indonesia Inc. Ltd

Mulia, Muhammad Fadli (2016) Pengurangan Insiden Energi Arc Flash Dengan Menggunakan Metode Zone Selective Interlocking Pada PT. Conocophilips Indonesia Inc. Ltd. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[img]
Preview
Text
2213106055-Undergraduate-Theses.pdf

Download (4MB) | Preview

Abstract

Sistem Electric Submersible Pump (ESP) memiliki arus hubung singkat yang khas jika dibandingkan sistem pada fasilitas lain. Hal ini dikarenakan, pada sistem ESP menggunakan kabel yang panjang untuk menyalurkan daya dari bagian permukaan ke bagian dasar sumur. Panjang kabel sistem ESP menyebabkan arus hubung singkat dan Arc Flash bagian dasar sumur dengan bagian permukaan memiliki beda yang cukup besar yaitu pada lajur tipikal 3 sebesar 78.70%. Besar insiden Arc Flash yang dilepaskan dapat merusak peralatan dan terutama dapat membahayakan pekerja yang bekerja di lingkungan tersebut. Perlu sistem pengaman yang mampu mengatasi gangguan tersebut. Zone Selective Interlocking sebagai sebuah metode yang bekerja berdasarkan komunikasi antar pengaman menjadi solusi yang sesuai dengan permasalahan tersebut. ZSI dapat mengurangi insiden energi Arc Flash tanpa mengorbankan selektifitas dari koordinasi pengaman sehingga kontinuitas daya tetap terjaga. Penerapan teknik ZSI ini akan coba diterapkan pada sistem tegangan rendah 0.48 kV PT. Conoco Phillips Indonesia Inc. Ltd. mengingat pentingnya perusahaan tersebut mengamankan peralatan serta pekerjanya dari insiden Arc Flash yang besar. ================================================================================== Sistem of Electric Submersible Pump (ESP) has a special characteristic for short circuit current compared to other industrial facilities. This is because, the ESP sistem uses a long cable to distribute power from the surface to the bottom of the well. The cable length of ESP sistem causes a short circuit current and Arc Flash in the bottom well and the surface have a big difference in the typical 3 is 78.70%. Incident energi released can damage equipment and endanger workers employed in these environments. We need a protection sistem that is able to cope with the disorder. Zone Selective Interlocking as a method based on the communication between protective device give solutions that fit the problem. ZSI can reduce Arc Flash incident energi without sacrificing selectivity of protection coordination so that the continuity of power is still safe. So we try apply this ZSI to the low voltage sistem 0,48 kV PT. Conocophillips Inc. Ltd. to give secure for workers and the equipment from high Arc Flash incident energi

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.310 289 Mul p
Uncontrolled Keywords: Arc Flash; Zone Selective Interlocking; Electric Submersible PumpArc Flash; Protection; Selective Coordination
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering