Studi Eksperimental "Insitu Condition" Pengaruh Penambahan Fin Setengah Silinder yang Dimiringkan 67.5º Sebagai Extended Surface dan Vortex Generator pada Bagian Bawah Plat Absorber Berbentuk V Terhadap Efisiensi Kolektor Surya Pemanas Udara

Oktyasworo, Harlista Dwi (2018) Studi Eksperimental "Insitu Condition" Pengaruh Penambahan Fin Setengah Silinder yang Dimiringkan 67.5º Sebagai Extended Surface dan Vortex Generator pada Bagian Bawah Plat Absorber Berbentuk V Terhadap Efisiensi Kolektor Surya Pemanas Udara. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2113100049_Undergraduate_Theses.pdf]
Preview
Text
2113100049_Undergraduate_Theses.pdf - Accepted Version

Download (6MB) | Preview

Abstract

Seiring dengan perkembangan teknologi yang semakin pesat kebutuhan terhadap energipun semakin meningkat. Konsumsi energi saat ini cukup mudah didapat karena masih banyak sumber-sumber daya alam yang memadai. Namun jika penggunaan energi tidak dikontrol dan digunakan secara terus menerus, maka sumber-sumber energi konvensional tersebut akan habis dan menyebabkan kerusakan lingkungan yang cukup parah. Oleh karena itu, sumber-sumber energi yang lain seperti energi matahari terus dikembangkan karena sangat murah dan mudah didapat. Energi matahari salah satunya dapat diaplikasikan pada kolektor pemanas udara yang berfungsi sebagai pengering. Sistem kerja pada kolektor tersebut yaitu dengan memanfaatkan radiasi dari matahari yang diserap malalui plat absorber, kemudian akan memindakan panas secara konveksi pada fluida yang mengalir dalam ducting.
Dalam upaya peningkatan efisiensi thermal kolektor surya pamanas udara, dilakukan modifikasi berupa memperluas bidang penyerapan menggunakan v-corrugated absorber dan meningkatkan koefisien perpindahan panas konveksi dengan menciptakan turbulensi pada area perpindahan panas. Gangguan berupa obstacle akan digunakan guna mendapatkan turbulensi aliran dengan memberikan segitiga tegak yang ditekuk 30o. Selain itu ditambahkan pula fin berbentuk setengah silinder berdiameter 6mm yang dimiringkan dengan sudut sebesar 66,7º terhadap arah aliran pada saluran fluida kerja dibawah plat penyerap panas guna menambah luasan perpindahan panas. Eksperimen tersebut akan dilakukan pada kondisi “insitu” dengan variasi laju aliran massa sebesar 0.02 kg/s; 0.03 kg/s; 0.05 kg/s dan 0.06 kg/s dan intensitas radiasi sesuai pada kondisi saat percobaan dilaksanakan.
Dari hasil pengujian eksperimental ini didapatkan bahwa pada kolektor surya pemanas udara dengan v-corrugated absorber besarnya energi berguna yang diserap oleh fluida kerja sebanding dengan laju alir massa dan intensitas radiasi. Q¬usefull paling tinggi dicapai pada laju aliran massa 0,06 kg/s dengan intensitas radiasi 915 Watt/m2 yakni 838,59 Watt. Sedangkan besarnya efisiensi berbanding lurus dengan peningkatan laju aliran massa namun berbanding terbalik dengan intensitas radiasi. Efisiensi tertinggi sebesar 99,44% dicapai pada laju aliran massa 0,05 kg/s dengan intensitas radiasi sebesar 654 Watt/m2.

===========================================================================================================

Along with the development of technology that rapidly growing the human needing for energy also increases. Current energy consumption is fairly easy to get, because there are still many natural resources are adequate. But if energy use is not controlled and used continuously, then the conventional energy sources will run out and cause damage to the environment is quite severe. Therefore, sources of energy such as solar energy continues to be developed because it is very cheap and easy to get it around the earth. Solar energy, one can be applied to the air heater collectors that functions as a dryer. Work on the collector system, namely by making use of radiation from the Sun is absorbed by the absorber plate, then be transferred heat convection in a fluid that flows in the ducting.
In an effort to increase the efficiency of thermal solar collectors heating the air, carried out the modification in the form of expanding the field of absorption using v corrugated absorber and improve heat transfer coefficient with convection creates turbulence on heat transfer area. Disturbances in the form of obstacle will be used in order to get the turbulence of the flow by giving an upright triangle bent 30º. Additionally added a half-cylinder-shaped fin diameter 6 mm which is tilted by an angle of 66,7º against direction of flow on the working fluid channels under the heat sink plate to add to the heat transfer area. The experiment will be carried out on conditions of "in situ" with variations of the mass flow rate of 0.02 kg/s; 0.03 kg/s; 0.05 kg/s dan 0.06 kg/s and corresponding radiation intensity on the conditions when the experiment was carried out.
From the experiment of v-corrugated absorber air heater solar collector the amount of useful energy absorbed by working fluid is directly proportional to the increase in mass flow rate and radiation intensity. The highest Quseful is achieved at mass flow rate of 0.06 kg/s with radiation intensity 915 Watt/m2 is 838.59 Watt. While the amount of solar collector efficiency is proportional to the increase in mass flow rate but inversely proportional to the radiation intensity. The highest efficiency is 99.44% is achieved at mass flow rate 0.05 kg/s with radiation intensity 654 Watt/m2.

Item Type: Thesis (Undergraduate)
Additional Information: RSM 621.472 Okt s-1
Uncontrolled Keywords: effisiensi, fin, intensitas radiasi, kolektor, laju aliran massa, obstacle, plat absorber
Subjects: T Technology > TJ Mechanical engineering and machinery
Divisions: Faculty of Industrial Technology > Mechanical Engineering > 21201-(S1) Undergraduate Thesis
Depositing User: HARLISTA DWI OKTYASWORO
Date Deposited: 12 Mar 2018 01:52
Last Modified: 26 Jun 2020 03:44