Analisa Karakteristik Minyak isolasi Transformator Daya 11kVA Menggunakan Meode DGA dan Breakdown Voltage Pada Gardu Kilang Pertamina RU-II Dumai

Akbar, Muhammad Fachry (2018) Analisa Karakteristik Minyak isolasi Transformator Daya 11kVA Menggunakan Meode DGA dan Breakdown Voltage Pada Gardu Kilang Pertamina RU-II Dumai. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111340000170-Undergraduate-Theses.pdf]
Preview
Text
07111340000170-Undergraduate-Theses.pdf - Accepted Version

Download (2MB) | Preview

Abstract

Studi ini dilakukan untuk mengetahui kegagalan yang terjadi pada transformator yang terdapat pada gardu kilang Pertamina RU-II Dumai dengan menggunakan metode DGA (Dissolved Gas Analysis) dan menganalisa karakteristik dari minyak transformator dengan menggunakan metode Breakdown Voltage. Terdapat 2 transformator yang akan diuji untuk mengetahui keadaan yang sedang terjadi pada transformator tersebut. Pengujian dilakukan pada laboratorium yang terdapat pada kilang Pertamina RU-II Dumai. Dari hasil pengujian dilakukan analisa dengan cara dengan membandingkan hasil pengujian yang telah dilakukan dengan data yang terdapat pada Pertamina RU-II Dumai. Pada metode DGA dilakukan perhitungan dengan metode interpretasi untuk mengetahui permasalahan yang terjadi. Dengan dilakukan pengujian dan perbandingan, diharapkan akan mengetahui lebih jelas permasalahan yang dapat terjadi pada transformator yang terdapat pada kilang Pertamina RU-II Dumai.
Pada pengujian dengan menggunakan metode Breakdown Voltage didapatkan nilai tegangan tembus yang cukup kecil karena memang nilai rating dari transformator tersebut yang cukup kecil. Kemudian untuk pengujian DGA (Dissolved Gas Analysis), pada transformator 1 memang sedang terjadi permasalahan yang pada saat pengambilan sampel transformator 1 dalam keadaan mati. Hasil dari perhitungan TDCG, transformator 1 berada pada kondisi 4. Berbeda dengan transformator 2 yang berada pada kondisi 1.
============== This study was conducted to find out the failure that occurred in the transformer contained in the Pertamina RU-II Dumai refinery using DGA (Dissolved Gas Analysis) method and analyzing the characteristics of transformer oil by using Breakdown Voltage method. There are 2 transformers that will be tested to determine the current state of the transformer. The tests were conducted at the laboratory located at the Pertamina RU-II Dumai refinery. From the test results are analyzed by comparing the test results that have been done with the data contained in Pertamina RU-II Dumai. In the method of DGA done calculations by interpretation method to find out the problems that occur. By testing and comparison, it is hoped to know more clearly the problems that can occur in the transformer contained in the Pertamina RU-II Dumai refinery.
In the test using the Breakdown Voltage method obtained the value of the translucency voltage is quite small because the value of the transformer is quite small. Then for testing DGA (Dissolved Gas Analysis), on the transformer 1 is going on a problem that at the time of sampling transformer 1 in a state of death. Results from TDCG calculations, transformer 1 is in condition 4. While the transformer 2 is in condition 1.

Item Type: Thesis (Undergraduate)
Uncontrolled Keywords: Transformator, Dissolved Gas Analysis (DGA), Breakdown Voltage
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1001 Production of electric energy or power
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK6565.T7 Transformers
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Akbar Muhammad Fachry
Date Deposited: 02 Oct 2018 02:22
Last Modified: 12 Mar 2021 00:26
URI: http://repository.its.ac.id/id/eprint/52669

Actions (login required)

View Item View Item