Analisis Laju Perpindahan Panas Dan Efektivitas Kondensor Unit IV PLTU PT PJB UP Gresik

Wijaya, Senna Oktovan (2019) Analisis Laju Perpindahan Panas Dan Efektivitas Kondensor Unit IV PLTU PT PJB UP Gresik. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 10211500000091-Non_Degree.pdf]
Preview
Text
10211500000091-Non_Degree.pdf

Download (5MB) | Preview

Abstract

PT PJB UP Gresik adalah salah satu perusahaan jasa dibidang produksi tenaga listrik yang berada di kawasan industri Gresik. Jumlah daya yang dihasilkan oleh perusahaan ini sebesar 2.260 Megawatt (MW) yang terdiri dari dua unit pembangkit listrik tenaga gas dan uap.PT PJB up Gresik mempunyai peralatan-peralatan pendukung produksinya. Diantara pendukungnya adalah kondensor.
Kondensor merupakan salah satu jenis heat exchanger yang berfungsi mengkondensasikan fluida gas menjadi cair. Kondensor adalah komponen utama pada siklus PLTU yang menjadi penyebab terbesar terjadinya losses pada siklus dan dapat mempengaruhi efisiensi suatu pembangkit. Jika laju perpindahan panas rendah, mengakibatkan kerja netto akan semakin meningkat. Mengetahui peran kondensor sangat penting dalam suatu siklus, maka perlu dilakukan laju perpindahan panas dan efektivitas kondensor Unit 4 PLTU PT. PJB UP Gresik.
Data yang diambil dari tugas akhir ini adalah data rata-rata aktual selama 1 bulan yaitu bulan juni 2018. Metode perhitungan untuk analisa pengaruh tekanan vakum terhadap laju perpindahan panas dan efektivitas adalah Log Mean Temperature Different (LMTD) dan Effectiveness – Number of Transfer Unit (NTU).Dari hasil perhitungan, dengan data kevakuman yaitu 0,05985 bar pada bulan juni diketahui laju perpindahan panas sebesar 71,38211565 MW dengan efektivitas sebesar 0,9880793.Laju perpindahan panas pada kondensor dipengaruhi oleh kondisi kevakuman kondensor. Semakin tinggi kevakuman kondensor maka steam semakin mudah menuju kondensor sehingga meningkatkan performa kondensor.
================================================================================================
PT PJB UP Gresik is one of the service companies in the field of electric power production in the Gresik industrial area. The amount of power produced by this company is 2,260 Megawatts (MW) which consists of two gas and steam power plants. PT PJB up Gresik has production support equipment. Among the supporters is a condenser.
Condenser is one type of heat exchanger that functions to condense gas fluid to liquid. The condenser is the main component in the PLTU cycle which is the biggest cause of losses in the cycle and can affect the efficiency of a generator. If the heat transfer rate is low, the net work will increase. Knowing the role of the condenser is very important in a cycle, it is necessary to do the heat transfer rate and the effectiveness of the 4PT Unit condenser. PLTU UP Gresik.
The data taken from this final project is the actual average data for 1 month, June 2018. The calculation method for analyzing the effect of vacuum pressure on heat transfer rate and effectiveness is Log Mean Temperature Different (LMTD) and Effectiveness - Number of Transfer Units ( NTU).From the results of calculations, with vacuum data which is 0.05985 bars in June it is known that the heat transfer rate is 71.38211565 MW with an effectiveness of 0.9880793. The heat transfer rate on the condenser is influenced by the condenser vacuum condition. The higher the vacuum condenser, the easier the steam to go to the condenser so that it increases the performance of the condenser.

Item Type: Thesis (Undergraduate)
Additional Information: RSMI 621.402 2 Wij a-1 2019
Uncontrolled Keywords: Kondensor, Tekanan Vakum, Laju Perpindahan Panas, Efektivistas
Subjects: T Technology > TJ Mechanical engineering and machinery > TJ263 Heat exchangers
Divisions: Faculty of Vocational > Mechanical Industrial Engineering