Studi Numerik Tentang Unjuk Kerja Heat Recovery Steam Generator Tipe Vertikal Dengan Variasi Sudut Pada Double Additional Turning Vane Di Inlet Transition Zone

Oktriyuda, Rozi (2020) Studi Numerik Tentang Unjuk Kerja Heat Recovery Steam Generator Tipe Vertikal Dengan Variasi Sudut Pada Double Additional Turning Vane Di Inlet Transition Zone. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 02111640000083_Undergraduate_Thesis.pdf]
Preview
Text
02111640000083_Undergraduate_Thesis.pdf

Download (7MB) | Preview

Abstract

Dengan perkiraan permintaan energi dunia naik sebesar 55% dari tahun 2005 sampai 2030, perancangan teknologi pembangkit energi yang baik sangatlah membantu untuk pemenuhan permintaan tersebut. Pembangkit Listrik Tenaga Gas dan Uap (PLTGU) Muara Karang blok 1 yang beroperasi selama 23 tahun sejak 1995 sampai 2018 mengalami penurunan total produksi uap sebesar 6.34% sehingga menurunkan produksi listrik di sistem turbin uap. Untuk temperatur exhaust gas outlet economiser mengalami kenaikan 40,86 oC. Dari penelitian-penelitian terdahulu tentang HRSG dapat diduga bahwa aliran flue gas di HRSG PLTGU Muara Karang blok 1 mempunyai distribusi kecepatan dan distribusi temperatur yang tidak merata atau non-uniform. Tugas akhir ini bertujuan untuk mengetahui bagaimana karakterisktik aliran flue gas di HRSG serta pengaruh penambahan turning vane di inlet transition zone HRSG terhadap distribusi temperatur, distribusi kecepatan dan Pressure drop. Tugas akhir ini dilakukan dengan memodelkan sampai proses Meshing HRSG menggunakan software Gambit 2.4.6 dan mensimulasikan-nya menggunakan software Ansys 19.1. Tube banks heat exchanger dimodelkan sebagai Porous medium sebagai fungsi dari Pressure drop dan ungroup macro heat exchanger, ntu model sebagai fungsi dari perpindahan panas. Penyederhanaan ini bermaksud untuk memudahkan dalam pengambilan data simulasi yang memakan waktu lama serta ukuran file yang begitu besar. Hasil yang didapat dari simulasi numerik bahwa penambahan 2 turning vane pada modifikasi 1 (sudut 15o dan 15o) di sisi inlet transition zone dapat meningkatkan penyerapan energi tertinggi pada HRSG sebesar 0,235%. Sedangkan untuk modifikasi 2 dan 3 meningkatkan penyerapan energi sebesar 0,09% dan 0,05%. Penambahan 2 turning vane di sisi inlet transition zone juga dapat membuat distribusi kecepatan dan temperatur flue gas lebih merata serta meningkatkan nilai dari pressure drop.
==================================================================================================================
With the estimated world energy demand up by 55% from 2005 to 2030, good energy generation technology design is very helpful for the fulfillment of such demands. The Gas and Steam power Plant (PLTGU) of Muara Karang Block 1 which operates for 23 years since 1995 to 2018 suffered a total decrease in steam production by 6.34% thereby lowering the production of electricity in the steam turbine system. For exhaust gas outlet Economizers temperature increased by 40.86 0C. From previous studies about HRSG can be suspected that the flow of flue gas in HRSG PLTGU Muara Karang Block 1 has a distribution of speed and distribution of uneven or non-uniform temperature s. This final task aims to determine how the characteristics of flue gas flow in HRSG as well as the influence of turning vane in the inlet transition zone HRSG to temperature distribution, speed distribution and Pressure drop.
This final project is carried out by modeled until the HRSG Meshing process using the Gambit 2.4.6 software and simulate it using the Ansys software 19.1. The heat exchanger Tube banks are modeled as Porous medium as the function of Pressure drop and ungroup macro heat exchanger, NTU model as a function of heat transfer. It intends to facilitate the retrieval of long time-consuming simulation data and large file size.
The results obtained from the numerical simulation that the addition of 2 turning vane in 1st modification (15o angle and 15o) on the side of the inlet transition zone can increase the highest energy absorption at HRSG by 0.235%. As for 2nd and 3rd modifications increase energy absorption by 0.09% and 0.05%. The addition of 2 turning vane in the side inlet transition zone can also make the distribution of speed and temperature of flue gas more uniform and increase the value of pressure drop.

Item Type: Thesis (Other)
Uncontrolled Keywords: velocity distribution, temperature distribution, Pressure drop, turning vane, heat exchanger, distribusi kecepatan, distribusi temperatur, Pressure drop, turning vane, heat exchanger.
Subjects: T Technology > TD Environmental technology. Sanitary engineering > TD899.S68 Steam power plants
Divisions: Faculty of Industrial Technology > Mechanical Engineering > 21201-(S1) Undergraduate Thesis
Depositing User: Rozi Oktriyuda
Date Deposited: 24 Aug 2020 07:37
Last Modified: 02 Oct 2023 06:20
URI: http://repository.its.ac.id/id/eprint/79472