Kondensor merupakan salah satu komponen pada pembangkit listrik tenaga uap (PLTU) yang berfungsi untuk mengubah uap air (vapor) yang keluar dari turbin, menjadi fasa cair (liquid). Fungsi dari perubahan fasa ini adalah untuk mengurangi tekanan pada bagian keluaran dari turbin agar efisiensi dari turbin meningkat. Salah satu jenis kondensor adalah kondensor shell and tube, atau biasa disebut dengan surface condenser. Dua hal yang dapat mempengaruhi performa kondensor adalah susunan pipa (tube) dan kecepatan aliran uap air pada sisi cangkang (shell). Analisa performa kondensor dapat dilakukan dengan menggunakan metode CFD (Computational fluid dynamics) yang merupakan salah satu cara untuk menyelesaikan suatu persamaan-persamaan yang berkaitan dengan dinamika fluida menggunakan perangkat komputer. Dalam penelitian ini dilakukan simulasi Surface Condenser dengan konfigurasi triangular dan rotated square pada kecepatan aliran uap 2,5 m/s dan 5 m/s. Temperatur uap masuk yang digunakan adalah 50 ºC. Simulasi dilakukan pada kondisi tekanan 0,12 bar dan temperatur saturasi 50 ºC. Material pipa yang digunakan adalah titanium. Temperatur pada permukaan pipa dipertahankan konstan dan homogen sebesar 25 ºC. Dari simulasi yang dilakukan didapatkan hasil bahwa performa konfigurasi triangular lebih baik di bandingkan dengan rotated square. Pada kecepatan aliran uap 2,5 m/s terjadi peningkatan heat transfer coefficient sebesar 5,94%, sedangkan pada kecepatan aliran uap 5m/s terjadi peningkatan heat transfer coefficient sebesar 6,55%. Dari simulasi juga didapatkan hasil bahwa condensation rate untuk konfigurasi triangular lebih baik dibandingkan dengan konfigurasi rotated square. Pada kecepatan aliran uap 2,5 m/s terjadi peningkatan sebesar 20,12%, sedangkan pada kecepatan aliran uap 5 m/s terjadi peningkatan sebesar 11,73%. Kecepatan aliran uap yang lebih tinggi menghasilkan nilai heat transfer coefficient yang lebih tinggi. Pada konfigurasi triangular terjadi peningkatan sebesar 14,71% sedangkan pada konfigurasi rotated square terjadi peningkatan sebesar 14,06%.
=====================================================================================================
The condenser is one of the components in a steam power plant (PLTU) which functions to convert water vapor (vapor) that comes out of the turbine, into the liquid phase (liquid). The function of this phase change is to reduce the pressure at the output of the turbine so that the efficiency of the turbine increases. One type of condenser is the shell and tube condenser, or commonly known as the surface condenser. Two things that can affect the condenser performance are the arrangement of the pipe (tube) and the velocity of water vapor flow on the shell side. Condenser performance analysis can be done using the CFD (Computational fluid dynamics) method, which is one way to solve equations related to fluid dynamics using a computer device. In this research, a Surface Condenser simulation with triangular and rotated square configurations was carried out at a vapor flow velocity of 2.5 m / s and 5 m / s. The temperature of the intake steam used was 50 ºC. The simulation was carried out at a pressure condition of 0.12 bar and a saturation temperature of 50 ºC. The pipe material used is titanium. The temperature at the pipe surface is maintained constant and homogeneous at 25 ºC. From the simulation, the results show that the performance of the triangular configuration is better than the rotated square. At the steam flow velocity of 2.5 m / s, there was an increase in the heat transfer coefficient by 5.94%, while at the steam flow rate of 5m / s there was an increase in the heat transfer coefficient by 6.55%. The simulation also shows that the condensation rate for the triangular configuration is better than for the rotated square configuration. At the steam flow velocity of 2.5 m / s there was an increase of 20.12%, while at the steam flow velocity of 5 m / s there was an increase of 11.73%. A higher vapor flow rate results in a higher heat transfer coefficient value. In the triangular configuration there was an increase of 14.71%, while in the rotated square configuration there was an increase of 14.06%.

Item Type: Thesis (Undergraduate)
Uncontrolled Keywords: Kondensasi, Surface Condenser, CFD, Condensation, Surface Condenser, CFD
Subjects: Q Science > QC Physics > QC320 Heat transfer
T Technology > TJ Mechanical engineering and machinery > TJ263 Heat exchangers
Divisions: Faculty of Industrial Technology and Systems Engineering (INDSYS) > Mechanical Engineering > 21201-(S1) Undergraduate Thesis