Simulasi Gate Cycle Pengaruh Aliran Massa Dan Posisi Ekstraksi Turbine Terhadap Peforma Pembangkit Listrik Tenaga Uap 200 MW PT.PJB Gresik Unit Pembangkit 3

Pradigdo, Daniel Adi (2015) Simulasi Gate Cycle Pengaruh Aliran Massa Dan Posisi Ekstraksi Turbine Terhadap Peforma Pembangkit Listrik Tenaga Uap 200 MW PT.PJB Gresik Unit Pembangkit 3. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2109100096-Undergraduate thesis.pdf]
Preview
Text
2109100096-Undergraduate thesis.pdf - Published Version

Download (2MB) | Preview

Abstract

Pembangkit Listrik Tenaga Uap (PLTU) merupakan
pembangkit listrik yang paling banyak digunakan di Indonesia.
PLTU sudah banyak mengalami evaluasi. Evaluasi yang
dilakukan ini bertujuan untuk meningkatkan effisiensi
pembangkit, jika effisiensi pembangkit semakin meningkat maka
konsumsi bahan bakar dari suatu pembangkit akan menurun.
Salah satu produsen listrik di Indonesia adalah PLTU gresik unit
3 merupakan pembangkit listik yang memiliki kapasitas rata-rata
sebesar 200 MW. Daya sebesar 200 MW tersebut dihasilkan
melalui tiga turbin yang dipasang pada satu poros, yang terdiri
dari HP (High Pressure), IP (Intermediate Pressure),dan LP
(Low Pressure). Pada unit pembangkit tiga tersebut digunakan 2
jenis sistem feedwater heater yaitu di antaranya 7 closed
feedwater heater dan 1 open feedwater heater. Pada tugas akhir
ini akan dicari bagaimana pengaruh variasi aliran massa dan
posisi ekstraksi turbin terhadap peforma pembangkit listrik.
Analisa yang digunakan pada tugas akhir ini
menggunakan analisa termodinamika, ASME PTC 7 dan dibantu
dengan software Gate Cycle 5.6. Gate cycle merupakan software
yang dapat memprediksi design pembangkit yang dimodelkan.
Data pembangkit existing di dapat dari P&ID. Dari P&ID
vi
tersebut dibangun pemodelan pembangkit yang dibuat
menyerupai keadaan pembangkit dalam keadaanya nyata. Setelah
pemodelan dilakukan, maka hal selanjutnya yang dilakukan
adalah memvariasikan kombinasi aliran massa dan variasi
posisi. Setelah itu dilakukan perbandingan hasil antara
perhitungan dengan hasil yang di dapat dari Gate Cycle. Hal
tersebut dilakukan agar dapat diketahui error (beda) yang terjadi
antara perhitungan dengan pemodelan. Setelah itu dilakukan
analisa pada variasi yang menunjukan heat rate yang mempunyai
nilai kecil serta power yang tinggi.
Pada analisa posisi ekstraksi terbaik terdapat pada posisi
1-4 dan variasi aliran massa yang terbaik terdapat pada 8% dan
8%. Variasi posisi terjelek terdapat pada posisi 3-4 dengan
aliran massa
============================================================================================
Steam Power Plant (Plant) is a power plant that is most
widely used in Indonesia. Plant has undergone many evaluations.
This evaluation aims to improve plant efficiency, if efficiency
power plant increasing, the fuel consumption of a plant will be
decreasing. One of the producers of electricity in Indonesia is
gresik Plant unit 3 is an electric generator which has an average
capacity of 200 MW. Power of 200 MW is generated by three
turbines are mounted on a single shaft, which consists of HP
(High Pressure), IP (Intermediate Pressure), and LP (Low
Pressure). In the three generating units are used two types of
feedwater heater system that is in between 7 closed feedwater
heater and one open feedwater heater. In this final project will
look for how the influence of variations in the mass flow and the
position of the extraction turbine power plants Performance.
The analysis used in this thesis using the thermodynamic
analysis, ASME PTC 7 and assisted with software Gate Cycle 5.6.
Gate cycle is a software that can predict the modeled plant
design. The data in the existing plant can be of the P & ID. From
P & ID modeling has bulit like the plant in real codition. Once
the modeling is done, then the next thing to do is to vary the
combination of mass flow and the variation of the position. After
that is done a comparison between the calculation results with
viii
obtained from Gate Cycle. This is done in order to know the error
(difference) which occurs between the modeling calculations.
Once that is done the analysis on heat rate variation shows that
have little value as well as high power.
Based on power analysis performed, validation
thermodynamic calculations with the results shown by the gate
cycle of 0.02%, while the rate of heat analysis of the errors that
occur at 0.1652%. While the analysis of the position of the best
extraction contained in position 1-4 and the best mass flow
variation present in 8% and 8%.

Item Type: Thesis (Undergraduate)
Additional Information: RSM 621.312 132 Pra s
Uncontrolled Keywords: Effisiensi Pembangkit, posisi ekstraksi, variasi aliran massa, heat rate, power
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission
T Technology > TJ Mechanical engineering and machinery > TJ164 Power plants--Design and construction
T Technology > TJ Mechanical engineering and machinery > TJ217.6 Predictive Control
Divisions: Faculty of Industrial Technology > Mechanical Engineering > 21201-(S1) Undergraduate Thesis
Depositing User: Mr. Tondo Indra Nyata
Date Deposited: 08 Jun 2017 06:34
Last Modified: 24 Aug 2018 04:14
URI: http://repository.its.ac.id/id/eprint/41536

Actions (login required)

View Item View Item