Analisa Arc Flash Pada Sistem Kelistrikan Di Pt. Ispat Indo Sidoarjo – Jawa Timur

Suparyo, Joko (2016) Analisa Arc Flash Pada Sistem Kelistrikan Di Pt. Ispat Indo Sidoarjo – Jawa Timur. Undergraduate thesis, Institut Teknologi Sepuluh Nopember Surabaya.

[thumbnail of 2212106093-Undergraduate_Thesis.pdf]
Preview
Text
2212106093-Undergraduate_Thesis.pdf - Published Version

Download (4MB) | Preview

Abstract

Arc Flash merupakan total energi yang dilepaskan ketika terjadi gangguan hubung singkat. Energi akan dilepaskan melalui udara mengalir ke fasa lain , netral atau mengalir ke tanah. Ketika pekerja yang tidak dilengkapi alat pelindung diri berada di dekat dengan Arc Flash, maka akan menyebabkan cedera serius dan bahkan kematian. Berdasarkan standar IEEE 1584-2002 yang mengatur tentang analisa bahaya busur api pada sistem tegangan rendah dan menengah, pengguna dapat dengan mudah menentukan batas keamanan untuk para pekerja. Menurut rekomendasi standar IEEE perhitungan arus hubung singkat selalu memperhatikan kontribusi arus gangguan dari generator, motor induksi dan sinkron. Besar kecilnya energi arc flash dapat ditentukan dari beberapa sudut pandang. Diantaranya ialah nilai energi arc flash akan besar apabila dihitung dengan menggunakan arus bolted three phase fault, sedangkan dari sudut arc clearing time yang didapat dari waktu dimana arus gangguan saat itu terjadi akan menghasilkan nilai energi busur api yang lebih rendah. Untuk mengurangi atau menurunkan nilai dari arc clearing time ini banyak metode yang digunakan, diantaranya adalah melakukan resetting koordinasi proteksinya serta pemasangan relai differential seperti yang dilakukan dalam tugas akhir ini. Untuk hasil yang didapat pada tugas akhir ini adalah pada tipikal 1 nilai insiden energi tertinggi 463.17 cal/cm2 turun menjadi 14.76 cal/cm2 , pada tipikal 2 nilai insiden energi tertinggi 68.95 cal/cm2 turun menjadi 6.97 cal/cm2 , pada tipikal 3 nilai insiden energi nya mengalami peningkatan yaitu dari 5.339 cal/cm2 menjadi 22.042 cal/cm2 kenaikan ini disebabkan karena terjadi kesalahan koordinasi rele
==============================================================================================Arc Flash is the total energy released when the short circuit . Energy is released through the air flowing into another phase , neutral or flows into the ground. When workers are not equipped with personal protective equipment be near the Arc Flash , it will cause serious injury and even death. Based on the IEEE 1584-2002 standard governing hazard analysis arcing at low and medium voltage systems , the user can easily determine the safety limit for workers. According to the recommendations of IEEE 1584-2002 standard short-circuit current calculation always looking at to the contribution of fault current from the generator , induction and synchronous motors. The size of the arc flash energy can be determined from the some of view point. Among them is the value of arc flash energy will be greater if calculated using three- phase bolted fault current , while from the corner arc clearing time obtained from the time where the fault current at the time it happens will generate arc energy value lower. To reduce or decrease the value of the arc clearing this time many of the methods used , like doing resetting the coordination of protection and installation of differential relays. The result obtained in this thesis is, in typical 1 the highest value of incident energy 463.17 cal/cm2 fell to 14.76 cal/cm2, in typical 2 the highest value of incident energy 68.95 cal/cm2 fell to 6.97 cal/cm2, in typical 3 the value of incident energy increased from 5.339 cal/cm2 to 22.042 cal/cm2, the increase is caused due to an error of relay coordination.

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.313 Jok a
Uncontrolled Keywords: Arc Flash, Arc clearing time, Arus bolted three phase fault, koordinasi proteksi, standar IEEE 1584-2002.
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1322.6 Electric power-plants
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: EKO BUDI RAHARJO
Date Deposited: 01 Apr 2020 06:26
Last Modified: 01 Apr 2020 06:26
URI: http://repository.its.ac.id/id/eprint/75648

Actions (login required)

View Item View Item