Back-Up Perlindungan Relay Jarak Zona Kedua Oleh Directional Overcurrent Relays Dengan Combined Curves

Nanda, Ariq Arsya (2016) Back-Up Perlindungan Relay Jarak Zona Kedua Oleh Directional Overcurrent Relays Dengan Combined Curves. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[img]
Preview
Text
2214105061-Undergraduate_Thesis.pdf - Accepted Version

Download (943kB) | Preview

Abstract

Dalam makalah ini, pendekatan baru untuk simultan pengaturan jarak dan relay arus lebih terarah. Ketika skema perlindungan garis terdiri dari relay jarak dan relay arus lebih terarah pengaturan relay harus dihitung mengingat kedua relay. Terpisah perhitungan estafet akan menyebabkan hilangnya selektivitas. Jika kedua zona waktu pengaturan adalah tetap, penentuan otomatis dari pengaturan bisa menyebabkan situasi yang tidak sesuai, serta menemukan satu set selektif pengaturan. Jadi zona waktu kedua harus diubah secara manual sampai masalah optimasi layak. Dalam metode ini, yang terbaik pengaturan untuk zona kedua yang membuat selektifitas dalam back-up dengan relay arus dapat menyebabkan waktu yang tidak menguntungkan dari zona kedua. Dalam metode yang diusulkan, bukannya mengubah waktu zona kedua, bentuk directional arus cadangan yang akan dirubah dengan lokasi gangguan dan saat ini. Ide mengatur proteksi rele arus dalam waktu respon pada arus kesalahan yang lebih tinggi dicapai dengan menggunakan perangkat perlindungan yang universal dengan platform perangkat lunak yang dapat memfasilitasi merancang waktu saat kurva karakteristik yang berbeda bentuk. Hasil simulasi menunjukkan efektivitas metode ini yaitu dengan mengkombinasi kurva rele arah arus lebih dengan relay jarak sehingga mendapatkan koordinasi yang tepat. ======================================================================================================================== In this paper, a novel approach for simultaneous setting of distance and directional overcurrent relays is presented. When the line protection schemes are composed of distance relays and directional overcurrent relays the setting of the relays must be computed considering both relays. Separate relay computation would lead to loss of selectivity. If the second zone time setting is fixed, automatic determination of the settings could lead to a non-feasible situation, indicating the impossibility of finding a selective set of settings. Thus the second zone time must be manually changed until the optimization problem is feasible. In this method, the best setting for the second zone that assures selectivity could be larger than the classical setting, so, it could lead to the unfavorable timing of the second zone. In the proposed method, instead of changing the time of the second zone, the shape of the backup directional overcurrent relay would be changed adaptively with the fault location and current. The idea of reducing the overcurrent protection response times at higher fault currents is achieved using a universal protection device with a software platform that can facilitate designing time-current characteristic curves of different shapes, all in the same hardware. The simulation results indicate the effectiveness of the method.

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.319 Nan b
Uncontrolled Keywords: Arus Hubung Singkat, Koordinasi Proteksi, Rele Arus Lebih, Rele Jarak
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays
Divisions: Faculty of Industrial Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: ansi aflacha
Date Deposited: 20 Feb 2020 02:16
Last Modified: 20 Feb 2020 02:16
URI: http://repository.its.ac.id/id/eprint/75060