Dalam makalah ini, pendekatan baru untuk simultan
pengaturan jarak dan relay arus lebih terarah. Ketika skema
perlindungan garis terdiri dari relay jarak dan relay arus lebih terarah
pengaturan relay harus dihitung mengingat kedua relay. Terpisah
perhitungan estafet akan menyebabkan hilangnya selektivitas. Jika
kedua zona waktu pengaturan adalah tetap, penentuan otomatis dari
pengaturan bisa menyebabkan situasi yang tidak sesuai, serta
menemukan satu set selektif pengaturan. Jadi zona waktu kedua harus
diubah secara manual sampai masalah optimasi layak. Dalam metode
ini, yang terbaik pengaturan untuk zona kedua yang membuat
selektifitas dalam back-up dengan relay arus dapat menyebabkan
waktu yang tidak menguntungkan dari zona kedua. Dalam metode
yang diusulkan, bukannya mengubah waktu zona kedua, bentuk
directional arus cadangan yang akan dirubah dengan lokasi gangguan
dan saat ini. Ide mengatur proteksi rele arus dalam waktu respon pada
arus kesalahan yang lebih tinggi dicapai dengan menggunakan
perangkat perlindungan yang universal dengan platform perangkat
lunak yang dapat memfasilitasi merancang waktu saat kurva
karakteristik yang berbeda bentuk. Hasil simulasi menunjukkan
efektivitas metode ini yaitu dengan mengkombinasi kurva rele arah
arus lebih dengan relay jarak sehingga mendapatkan koordinasi yang
tepat.
========================================================================================================================
In this paper, a novel approach for simultaneous setting of
distance and directional overcurrent relays is presented. When the line
protection schemes are composed of distance relays and directional
overcurrent relays the setting of the relays must be computed
considering both relays. Separate relay computation would lead to
loss of selectivity. If the second zone time setting is fixed, automatic
determination of the settings could lead to a non-feasible situation,
indicating the impossibility of finding a selective set of settings. Thus
the second zone time must be manually changed until the
optimization problem is feasible. In this method, the best setting for
the second zone that assures selectivity could be larger than the
classical setting, so, it could lead to the unfavorable timing of the
second zone. In the proposed method, instead of changing the time of
the second zone, the shape of the backup directional overcurrent relay
would be changed adaptively with the fault location and current. The
idea of reducing the overcurrent protection response times at higher
fault currents is achieved using a universal protection device with a
software platform that can facilitate designing time-current
characteristic curves of different shapes, all in the same hardware.
The simulation results indicate the effectiveness of the method.

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.319 Nan b
Uncontrolled Keywords: Arus Hubung Singkat, Koordinasi Proteksi, Rele Arus Lebih, Rele Jarak
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays
Divisions: Faculty of Industrial Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: ansi aflacha
Date Deposited: 20 Feb 2020 02:16
Last Modified: 20 Feb 2020 02:16
URI: http://repository.its.ac.id/id/eprint/75060

Actions (login required)

View Item View Item