Analisis Instalasi Pompa Pemadam Kebakaran di Terminal LPG Semarang dalam Memenuhi Standard NFPA 14

Iskandar, Muhammad Rickza Nuril (2020) Analisis Instalasi Pompa Pemadam Kebakaran di Terminal LPG Semarang dalam Memenuhi Standard NFPA 14. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 04211640000025-Undergraduate_Thesis.pdf]
Preview
Text
04211640000025-Undergraduate_Thesis.pdf

Download (2MB) | Preview

Abstract

Terminal LPG Semarang merupakan sebuah perusahaan yang bergerak di bidang minyak dan gas yaitu sebagai penerima, pencampur, penimbun, serta pendistribusian LPG ke berbagai wilayah di Jawa Tengah. Selama proses pengoperasiannya, Terminal LPG Semarang memiliki potensi berbahaya kebakaran. Untuk itu maka diperlukan suatu sistem pemadam kebakaran yang memadai dan sesuai dengan standard peraturan yang sudah ditetapkan. Salah satu peraturan yang mengatur hal tersebut yaitu tertuang pada National Fire Protetion Association (NFPA). Pada NFPA diatur beberapa peraturan khusus untuk LPG Plant. Pada NFPA 14 diatur mengenai nilai kapasitas aliran minimum pada setiap standpipe.
Selama ini Terminal LPG Semarang menjalankan sistem pemadam kebakaran menggunakan empat pompa pemadam kebakaran dengan kapasitas setiap pompa 3.000 GPM dikarenakan belum dilakukannya perhitungan nilai kapasitas aliran air yang keluar dari nozzle telah sesuai standard tersebut atau belum. Untuk itu maka dilakukannya penelitian ini yang bertujuan untuk mengetahui nilai kapasitas pada setiap nozzle dan memaksimalkan penggunaan pompa untuk memenuhi standard NFPA 14.
Dari hasil penelitian didapatkan nilai kapasitas pada 9 nozzle masih dibawah standard NFPA 14, kemudian didapatkan perhitungan kebutuhan nilai kapasitas dan head setiap pompa untuk memenuhi standard NFPA 14 yaitu, 4.960 GPM dengan head pompa lebih dari 72,5 m. 3. Alternatif penyelesaian yang paling baik diterapkan yaitu menggunakan pompa baru yang memiliki spek kapasitas pompa 5.000 GPM dan head pompa lebih dari 72,5 m.
=================================================================================================
Terminal LPG Semarang is a company engaged in the oil and gas as a receiving, mixing, storage and distribution of LPG to various regions in Central Java. During the operation process, Terminal LPG Semarang has the potential of fire hazard. Therefore, a fire extinguisher is required and in accordance with the standard regulations. One of the rules that govern this is stated in National Fire Protetion Association (NFPA). NFPA 14 regulates the minimum flow rates values for each standpipe.
During this time, the LPG Terminal Semarang has run a fire extinguisher system using four fire pumps with a capacity of 3,000 GPM for each pump because there is no calculation of the value of the flow of water coming out of the nozzle according to that standard or not. For this reason, this study was conducted which aims to determine the value of flow rates in each nozzle and maximize the use of pumps to meet NFPA 14 standards.
The results concluded that the value of capacity at 9 nozzles is still below the NFPA 14 standard, then the calculation of the capacity and head requirements of each pump is obtained to meet the NFPA 14 standard that is, 4,960 GPM with a pump head must be more than 72.5 m. The best alternative solution is to use a new pump that has a 5,000 GPM pump capacity and a pump head of more than 72.5 m.

Item Type: Thesis (Other)
Uncontrolled Keywords: nozzle, NFPA, pemadam kebakaran, pompa, terminal LPG, Fire Extinguisher; LPG Terminal; Nozzle; NFPA; Pump.
Subjects: T Technology > TJ Mechanical engineering and machinery > TJ903 Pumping machinery.
Divisions: Faculty of Marine Technology (MARTECH) > Marine Engineering > 36202-(S1) Undergraduate Thesis
Depositing User: Muhammad Rickza Nuril Iskandar
Date Deposited: 23 Aug 2020 06:41
Last Modified: 05 Nov 2023 16:19
URI: http://repository.its.ac.id/id/eprint/80296

Actions (login required)

View Item View Item