Harefa, Gamaliel Lizaro (2024) Analisis Kedip Tegangan pada Sistem Kelistrikan Sulawesi Bagian Selatan: Studi Kasus pada Beban Industri Smelter. Other thesis, Institut Teknologi Sepuluh Nopember.
Text
5022201186_Undergraduate_Thesis.pdf - Accepted Version Restricted to Repository staff only until 1 October 2026. Download (6MB) | Request a copy |
Abstract
Energi listrik adalah energi yang menjadi kebutuhan bagi manusia saat ini. Untuk mengoptimalkan daya yang tersalurkan, diperlukan suatu kualitas daya yang baik. Kualitas daya memberikan acuan atau parameter untuk pengiriman daya dari pembangkitan hingga menuju konsumen. Salah satu parameter yang dapat dipantau dari kualitas daya listrik adalah kualitas tegangan. Kualitas tegangan banyak dipengaruhi oleh beban non-linear, seperti beban motor, AVR, dan lain sebagainya. Saat ini, penggunaan beban non-linear dan sensitif meningkat akibat peningkatan kapasitas smelter di pulau Sulawesi. Peningkatan ini berpotensi dapat mengganggu tegangan pada sistem tenaga, seperti kedip tegangan atau voltage dip. Selain itu, gangguan pada sistem transmisi dapat berpotensi menyebabkan voltage dip pada beban sensitif, seperti smelter. Gangguan ini bersifat acak dan tidak dapat diketahui secara pasti. Tugas akhir ini akan membahas mengenai voltage dip pada salah satu beban smelter di sistem kelistrikan Sulawesi Bagian Selatan, baik karena gangguan pada smelter maupun gangguan pada sistem transmisi sekitar smelter. Gangguan yang disimulasikan berjenis 1 phase to ground, 2 phase to ground, dan 3 phase short circuit pada berbagai bus 150 kV secara acak. Nilai Voltage Dip akan dianalisis menggunakan standar IEEE 1668-2017. Menurut hasil analisis yang didapatkan dari voltage dip di sistem Sulawesi Bagian Selatan, gangguan beban smelter dapat menyebabkan Voltage Dip dengan besaran voltage dip sebesar 59% pada bus GI Bantaeng Smelter. Jika ditinjau dari gangguan pada sistem transmisi, bus GI Bantaeng Smelter mengalami voltage dip paling besar sebesar 40% akibat gangguan 3 phase short circuit GI Tallasa. Selain itu, lokasi gangguan yang dekat dengan beban smelter juga menyebabkan voltage dip yang lebih besar pada smelter dibandingkan dengan lokasi gangguan yang jauh.
============================================================
============================================================
Electrical energy is essential for humans today. To optimize the power delivered, good power quality is required. Power quality provides guidelines or parameters for delivering power from generation to consumers. One parameter that can be monitored is voltage quality, which is greatly influenced by non-linear loads such as motors, AVRs, etc. Currently, the use of non-linear and sensitive loads has increased due to the rising capacity of smelters in Sulawesi. This increase can potentially disrupt system voltage, causing Voltage Dips. Additionally, transmission system disturbances can cause Voltage Dips in sensitive loads like smelters. These disturbances are random and unpredictable. This thesis discusses voltage dip in a smelter load in the South Sulawesi electrical system, caused by both smelter and nearby transmission system disturbances. Simulated disturbances include single-phase to ground, two-phase to ground, and three-phase short circuits on various 150 kV buses randomly. Voltage Dip values are analyzed using IEEE 1668-2017 standards. The analysis shows that smelter load disturbances can cause Voltage Dips of 59% at the Bantaeng Smelter bus. For transmission system disturbances, the Bantaeng Smelter bus experiences a voltage dip of up to 40% due to a three-phase short circuit at the Tallasa substation. Additionally, disturbances near the smelter load result in greater Voltage Dips compared to those farther away.
Item Type: | Thesis (Other) |
---|---|
Uncontrolled Keywords: | Kualitas Daya, Voltage Dip, Industri Smelter, Sistem Transmisi, Power Quality, Transmission System |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK152.A75 Electrical engineering--Safety measures |
Divisions: | Faculty of Intelligent Electrical and Informatics Technology (ELECTICS) > Electrical Engineering > 20201-(S1) Undergraduate Thesis |
Depositing User: | Gamaliel Lizaro Harefa |
Date Deposited: | 25 Jul 2024 07:17 |
Last Modified: | 25 Jul 2024 07:17 |
URI: | http://repository.its.ac.id/id/eprint/109037 |