Analisa ARC Flash Pada Sistem Kelistrikan Di PT Wilmar Nabati Indonesia, Gresik-Jawa Timur

Nugroho, Aditya Aji (2017) Analisa ARC Flash Pada Sistem Kelistrikan Di PT Wilmar Nabati Indonesia, Gresik-Jawa Timur. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2212106059-Undergraduate_Thesis.pdf] Text
2212106059-Undergraduate_Thesis.pdf - Published Version
Restricted to Repository staff only

Download (10MB) | Request a copy

Abstract

Studi untuk mengetahui besar busur api yang dihasilkan pada masing-masing switchgear perlu dilakukan untuk mengklasifikasikan kategori energi busur api yang terjadi serta kaitannya dengan PPE (Personal Protective Equipment) yang harus dikenakan pekerja sebagai langkah pencegahan agar terhindar dari jatuhnya korban jiwa. Oleh karena itu perlu dilakukan perhitungan insiden energi arc flash sesuai standar IEEE 1584-2002 serta pengklasifikasian kategori dan alat perlindungan diri yang tepat agar memberikan rasa aman dan nyaman bagi para pekerja sehingga dapat bekerja secara optimal. Studi ini akan coba diterapkan pada sistem kelistrikan di PT. Wilmar Nabati Indonesia, Gresik – Jawa Timur mengingat pentingnya perusahaan tersebut mengamankan peralatan serta pekerjanya dari insiden energy arc flash. Hasil yang didapat pada tugas akhir ini adalah pada tipikal 1 nilai insiden energinya mengalami peningkatan yaitu dari 1.988 cal/cm2 menjadi 8.66 cal/cm2, pada tipikal 2 nilai insiden energi tertinggi 19.596 cal/cm2 turun menjadi 6.00 cal/cm2, pada tipikal 3 nilai insiden energi nya mengalami peningkatan yaitu dari 19.596 cal/cm2 menjadi 36.52 cal/cm2 kenaikan ini disebabkan karena terjadi kesalahan koordinasi rele.
------------------------------------------------------------------------------------------------------------------
Study to know large a arc that produced on each switchgear needs to be
done to classify category arc energy that occurs and relation to PPE
(Personal Protective Equipment) that must be worn workers as a
precautionary measure to avoid from death victim.. It is therefore
necessary the calculation of incidence energy arc flash according to
standard IEEE 1584-2002 and classify category and the self protection
exact to provide security and comfort to workers so as to be worked
optimally. This study will try to applied to of electric system in
PT.Wilmar Nabati Indonesia, Gresik - East Java considering the
importance of the company secure equipment and workers of incident
energy arc flash. The results obtained on their work end of this is on
typical 1 value incident energy increased from 1.988 cal / cm2 be 8.66
cal / cm2, In typical 2 the incident highest energy 19.596 cal / cm2 fell to
6.00 cal / cm2, in typical 3 the incident his energy increased from 19.596
cal / cm2 be 36.52 cal / cm2 this increase is because occurred misscoordination
rele.

Item Type: Thesis (Undergraduate)
Uncontrolled Keywords: Audio visual, Buku pedoman, Contoh, Deskripsi, Flash, Perpustakaan, Acr Flash, PPE (Personal Protective Equipment), Incident Energy, standard IEEE 1584-2002
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission
T Technology > T Technology (General) > T55 Industrial Safety